137
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
6
Continued on next page
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
A4 H
164 H
-
0
255
SPACE SENSOR TEMPERATURE (ROOM AIR) (1/10 DEGREES,
HIGH BYTE, 16 BIT VALUE, 0 = -40 DEGREES F)
A4 L
164 L
-
0
255
SPACE SENSOR TEMPERATURE (ROOM AIR) (1/10 DEGREES,
LOW BYTE, 16 BIT VALUE, 0 = -40 DEGREES F)
A5 L
165 L
3
0
5
SPACE SENSOR OFFSET RANGE (DEGREES)
A6 L
166 L
-
0
100
RETURN AIR HUMIDITY (%)
A7 L
167 L
-
0
100
OUTSIDE AIR HUMIDITY (%)
A8 H
168 H
-
0
255
DEMAND VENTILATION (IAQ) VALUE (PPM VALUE, HIGH BYTE)
A8 L
168 L
-
0
255
DEMAND VENTILATION (IAQ) VALUE (PPM VALUE, LOW BYTE)
A9 H
169 H
-
0
255
BUILDING PRESSURE VALUE (0.001” WC, HIGH BYTE, 0 = -0.250”
WC, MAX = 0.250” WC)
A9 L
169 L
-
0
255
BUILDING PRESSURE VALUE (0.001” WC, LOW BYTE, 0 = -0.250”
WC, MAX = 0.250” WC)
AA H
170 H
-
0
255
DUCT PRESSURE VALUE (0.01” WC, HIGH BYTE, 0 = 0.00” WC,
MAX = 5.00” WC)
AA L
170 L
-
0
255
DUCT PRESSURE VALUE (0.01” WC, LOW BYTE, 0 = 0.00” WC, MAX
= 5.00” WC)
AB H
171 H
0
0
200
REMOTE CONTROL INPUT VALUE (0.05 VDC COUNTS FOR
COOLING SAT SETPOINT SCALING)
AB L
171 L
40
0
200
DEMAND VENTILATION SETPOINT (25 PPM INCREMENTS,
MAXIMUM 5000 PPM)
AC L
172 L
80
0
200
AIR QUALITY (DV) SENSOR RANGE (25 PPM INCREMENTS,
MAXIMUM 5000 PPM)
AD L
173 L
60
0
240
UNOCCUPIED OVERRIDE TIME PERIOD (MINUTES)
AE H
174 H
45
0
100
OUTDOOR AIR TEMPERATURE COOLING LOCKOUT
TEMPERATURE (DEGREES F, 0 = DISABLED)
AE L
174 L
75
0
100
OUTDOOR AIR TEMPERATURE HEATING LOCKOUT
TEMPERATURE (DEGREES F, 0 = DISABLED)
AF H
175 H
50
40
65
SAT COOLING LIMIT SETPOINT (DEGREES F)
AF L
175 L
135
100
180
SAT HEATING LIMIT SETPOINT (DEGREES F)
B0 H
176 H
120
80
180
HYDRONIC HEATING STAGE #1 SUPPLY AIR SETPOINT (DEGREES
F)
B0 L
176 L
150
80
180
HYDRONIC HEATING STAGE #2 SUPPLY AIR SETPOINT (DEGREES
F)
B1 H
177 H
80
60
85
COMFORT VENTILATION UPPER SETPOINT (DEGREES F)
B1 L
177 L
70
60
85
COMFORT VENTILATION LOWER SETPOINT (DEGREES F)
B2 H
178 H
60
40
70
VAV COOLING SUPPLY AIR TEMPERATURE: UPPER SETPOINT
(DEGREES F)
B2 L
178 L
55
40
70
VAV COOLING SUPPLY AIR TEMPERATURE: LOWER SETPOINT
(DEGREES F)
B3 H
179 H
72
40
85
VAV COOLING SUPPLY AIR TEMPERATURE: RESET SETPOINT
(DEGREES F)
B3 L
179 L
68
40
85
VAV OCCUPIED HEATING SETPOINT (DEGREES F)
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...