YORK INTERNATIONAL
90
FORM 100.50-NOM1 (604)
Menu Navigation and Display Description
** OPERATION DATA **
Space Temperature
Temp = 71.2°F
Setpt = 71.0°F
** OPERATION DATA **
Building Pressure
Press = +0.08 inwg
Setpt = +0.10 inwg
** OPERATION DATA **
Outside Air Damper
Position #1 = 34%
Min Pos = 25%
** OPERATION DATA **
Outside Air Damper
Position #2= 30 %
Position #3= 35 %
** OPERATION DATA **
Outside Air Damper
Flow #1= 15478 CFM
** OPERATION DATA **
Outside Air Damper
Flow #2= 5732 CFM
** OPERATION DATA **
Outside Air Damper
TotalFlow= 21210 CFM
Setpt= 20000
** OPERATION DATA **
Demand Ventilation
Sensor= XXXX ppm
Setpt= XXXX ppm
Line 2 Space Temperature
Line 3 Temp = XX.X°F (0.0)
Line 4 Setpt = XX.X°F (0.0)
Line 2 Building Pressure
Line 3 Press = +/-X.XX inwg (0.0, ???)
Line 4 Setpt = +/-X.XX inwg (0.0)
Line 2 Outside Air Damper
Line 3 Position # 1 = XXX%
Line 4 Min Pos = XXX%
Line 2 Outside Air Damper
Line 3 Position #2= XXX %
Line 4 Position #3= XXX %
Line 2 Outside Air Damper
Line 3 Flow #1= XXXXX cfm (0.0)
Line 4
Line 2 Outside Air Damper
Line 3 Flow #2= XXXXX cfm (0.0)
Line 4
Line 2 Outside Air Damper
Line 3 TotalFlow= XXXXX cfm (0.0)
Line 4 Setpt= XXXXX cfm (0.0)
Line 2 Demand Ventilation
Line 3 Sensor Value= XXXX ppm (0)
Line 4 Setpt= XXXX ppm