YORK INTERNATIONAL
114
FORM 100.50-NOM1 (604)
Parameter Description and Options
43
Duct Static Pressure
inwg
1.5
0.00-5.00
Setpoint
44
Building Pressure
inwg
0.1
-0.4
Setpoint
45
Economizer 1st Stage
°F
55°
40°-65°
Setpoint
46
Economizer 2nd Stage
°F
50°
40°-65°
Setpoint
47
SAT Econo Load Heat
°F
150
100 – 195
Setpoint
48
Outside Air Enthalpy
btu/lb
28
22-40
Setpoint
49
Cmfrt Vent High SAT
°F
80°
60°-85°
Setpoint
50
Cmfrt Vent Low SAT
°F
70°
60°-85°
Setpoint
51
Warm-Up RAT
°F
70°
50°-85°
Setpoint
52
Hydro Heat 1st Stage
°F
100°
75°-150°
Setpoint
53
Hydro Heat 2nd Stage
°F
115°
75°-150°
Setpoint
54
OA Damper Min Pos #1
%
15%
0-100%
Setpoint
55
OA Damper Min Pos #2
%
30%
0-100%
Setpoint
56
Demand Ventilation
ppm
1000
750-1500
Setpoint
57
Min Outside Airfl ow
CFM
4000
0-15000
Setpoint
58
(FlexSys) MSAT Setpoint
°F
62
55 – 70
Setpoint
59
(FlexSys) Min Dewpt Diff
°F
3
1 – 5
Setpoint
60
Language Option
English
English, Spanish
Unit Setup
61
Measurement Units
Imperial
Imperial, SI Canada, SI
Unit Setup
62
Space Sensor Enable
OFF
ON or OFF
Unit Setup
63
Unocc Override Time
min
60 min
0-240 min
Unit Setup
64
Space Setpt Offset
°F
3°F
0°-5°F
Unit Setup
65
Fan ON With Sensor
ON
ON or OFF
Unit Setup
66
RAT Sensor Enable
OFF
ON or OFF
Unit Setup
67
Space Temp Alrm Diff
°F
5°F
0°-25°F
Unit Setup
68
Space Temp Alrm Time
min
60 min
0-120 min
Unit Setup
69
Low Ambient Operate
OFF
ON or OFF
Unit Setup
70
Sens Consist Enable
OFF
ON or OFF
Unit Setup
71
SAT Control For Cool
OFF
ON or OFF
Unit Setup
72
SAT Control For Heat
°F
OFF
ON or OFF
Unit Setup
73
Rev Act Heat Valve
OFF
ON or OFF
Unit Setup
74
Cooling Mode Enable
ON
ON or OFF
Unit Setup
75
Heating Mode Enable
ON
ON or OFF
Unit Setup
76
Heat Lockout OAT
°F
75°F
0°-100°F
Unit Setup
77
Cool Lockout OAT
°F
45°F
45°-100°F
Unit Setup
78
Cooling SAT Alarm
°F
0°F
0°/50°-80°F
Unit Setup
79
Heating SAT Alarm
°F
0°F
0°/70°-120°F
Unit Setup
80
Duct Pressure Limit
inwg
3.00 inwg
0.00-5.00 inwg
Unit Setup
81
VAV Occupied Heat
OFF
ON or OFF
Unit Setup
82
OA SAT Reset
OFF
ON or OFF
Unit Setup
83
SAT Temper Enable
OFF
ON or OFF
Unit Setup
84
VAV With Thermostat
ON
ON or OFF
Unit Setup
85
VAV Control Offset
°F
4.5
2.0 – 6.0
Unit Setup
Description Text On OCC
Units
Default
Value
Value
Range
OCC
Key
* Continued on next page
TABLE 21 – SETPOINTS AND VALUES (CONTINUED)