87
YORK INTERNATIONAL
FORM 100.50-NOM1 (604)
6
*** UNIT STATUS ***
Supply Fan System
Fan Status = ON
Cntrl Output = 78%
*** UNIT STATUS ***
Exhaust Fan System
Fan Status = ON
Cntrl Output = 100%
*** UNIT STATUS ***
Comp System #1
Status = SAFETY TRIP
Comps ON = NONE
*** UNIT STATUS ***
Hydronic Heat System
Cntrl Output = 0%
Freezestat = Normal
*** UNIT STATUS ***
Staged Heat System
Stages ON = 1
Stages Avail = 3
*** UNIT STATUS ***
Economizer System
Type = Single Enth.
Status = Inactive
Line 2 Supply Fan System
Line 3 Fan Status = ON (OFF or FAULT)
Line 4 Cntrl Output = XXX%
Line 2 Exhaust Fan System
Line 3 Fan Status = ON (OFF)
Line 4 Cntrl Output = XXX%
Line 2 Comp System #X
Line 3 Status = NORMAL (SAFETY TRIP)
Line 4 Comps ON = A (B, BOTH, NONE)
Display #7 repeats for compressor systems 2 and 3. If
the unit is a 4-stage (2 system) unit, system 3 data will
show N/A for Status and Comps ON.
Line 2 Hydronic Heat System
Line 3 Cntrl Output = XXX%
Line 4 Freezestat = NORMAL
(SAFETY TRIP)
Line 2 Staged Heat System
Line 3 Stages ON = X
Line 4 Stages Avail = X= 0-6
Line 2 Economizer System
Line 3 Type = (Single, Dual, Outside Air) N/A
Line 4 Status = Active (Inactive, N/A, Fault)
Line 3 displays one of the following economizer system
operation con
Þ
g u ra tions:
OA Dry Bulb
Single Enth (Single Enthalpy)
Dual Enthalpy
N/A (Unit is not equipped with an economizer or econ-
o miz er is not enabled)