YORK INTERNATIONAL
134
FORM 100.50-NOM1 (604)
Service
FAULT TITLE
RDU’s HISTORY
BUFFER
SET WHEN
RESET WHEN
SHUT
DOWN
(1)
GENERAL
STATUS
ADDITIONAL ACTIONS
or DISPLAYS
(3) (4)
TROUBLE
ALARM
TABLE 34 – FAULT DESCRIPTION TABLE (continued)
Tstat Cooling
Fault (10)
{Y1 = OFF} AND {Y2 = ON}
{Y1 AND Y2 = ON} OR
{Y1 AND Y2 = OFF}
*
––
Tstat Heating
Fault (10)
{W1 = OFF} AND {W2 = ON}
{W1 AND W2 = ON} OR
{W1 AND W2 = OFF}
*
––
Bldg Pressure
Fault
Unit is programmed for Power
Exhaust AND building static
pressure sensor is not reliable.
Building Pressure is
within the acceptable
range.
*
OpData/Building
Pressure Press = ???
(11)
OAT Sensor Fault
OAT sensor is not reliable.
OAT sensor is reliable.
(13)
*
OpData/OA Temp = ???
OpData/OA Enth = ???
Unit will Ignore htg & clg
lockouts, allow htg or clg,
& disable the Economizer
and other functions
dependent on OAT.
F/SLAB Sensor
Fault
FlexSys Dewpt reset
programmed for ON and Slab
Temp Input is unreliable.
FlexSys Dewpt Reset
programmed for OFF,
or Slab Temp Input is
reliable.
*
Control SAT to VAV High
Setpoint.
F/RH Sensor
Fault
FlexSys Dewpt Reset
programmed ON and Humidity
Sensor Input is unreliable
FlexSys Dewpt Reset
programmed for OFF,
or Humidity Sensor is
reliable
*
Control SAT to VAV High
Temp Setpoint.
OAH Sensor Fault
Unit programmed to read OAH
sensor AND OAH sensor is not
reliable.
Unit reprogrammed to
disable OAH sensor OR
OAH sensor is reliable.
*
OpData/OA RH = ???
OpData/OA Enth = ???
RAH Sensor Fault
Unit programmed to enable RAH
sensor AND RAH sensor is not
reliable.
Unit programmed to
disable RAH sensor or
RAH sensor is reliable.
*
OpData/RA RH = ???
OpData/RA Enth = ???
IAQ Sensor Fault
Unit programmed for
Economizer AND programmed
to enable IAQ sensor AND CO2
sensor is not reliable.
Unit programmed to
disable IAQ Sensor OR
CO2 sensor is reliable.
*
Demand Ventilation is not
permitted.
OA Flow Sensor
Fault
Unit programmed to enable
‘OA Flow Control’ AND Air fl ow
sensors are not reliable. (15)
Airfl ow sensors are
reliable.
*
OA Flow Control not
permitted.
Bad OAF
Transducer
Unit programmed to enable ‘OA
Flow Control’ AND following an
OA Flow Transducer Auto-Zero
Function, the transducers are
not within 10% of the sensor
range (i.e. > .05 in wg)}. (16)
Following subsequent
OA Flow Transducer
Auto-Zero Function,
transducers are <=
10% of full range for the
sensors.
*
OA Flow Control not
permitted.
SensConsist Fault
#1
During Sensor Consistency
check the SAT-(RAT+1.5F) is
greater than 3 OR RAT – Space
Temperature is greater than 3.
During Sensor
Consistency check the
SAT-(OAT+1.5F)] is
less than or equal to
3 OR Cycle power on
controller.
*
––