125
YORK INTERNATIONAL
FORM 100.50-NOM1 (604)
8
FIG. 51 –
SECONDARY CONTROLLER
00492VIP
FIG. 52 –
MOD-UNT WIRING DIAGRAM
LD06687
SECONDARY
CONTROLLER
(MOD-UNT)
CONDENSER FAN
VFD - SYSTEM NO. 1
OPTIONAL
CONDENSER FAN
VFD - SYSTEM NO. 2
OPTIONAL
CONDENSER FAN
VFD - SYSTEM NO. 3
OPTIONAL
2AO1
2AO1C
2AO2
2AO2C
2AO3
2AO3C
W3
W4
W8
W9
W14
W18
TB-4
W25
W1
W2
W5
W6
W10
W11
W12
W15
W16
W17
W21
W22
100
COM
1
2
24VAC
24VAC
RTN
RTN
1
2
3
N2+
N2-
N2 GND
2AI1
2AI1C
2AI2
2AI2C
2AI3
2AI3C
2AI4
2AI4C
2AI5
2AI5C
2AI6
2AI6C
15V(D)
15V(E)
15V(F)
15V(D)
15V(E)
15V(F)
SUCTION PRESSURE
TRANSDUCER SYSTEM #1
OPTIONAL
DISCHARGE PRESSURE
TRANSDUCER SYSTEM #1
OPTIONAL
SUCTION PRESSURE
TRANSDUCER SYSTEM #2
OPTIONAL
DISCHARGE PRESSURE
TRANSDUCER SYSTEM #2
OPTIONAL
SUCTION PRESSURE
TRANSDUCER SYSTEM #3
OPTIONAL
DISCHARGE PRESSURE
TRANSDUCER SYSTEM #3
OPTIONAL
OUT
COM
EXC
OUT
COM
EXC
OUT
COM
EXC
OUT
COM
EXC
OUT
COM
EXC
OUT
COM
EXC
TO MOD-DCU
TB2
W55
W56
* FIELD INSTALLED
2
1
5
3
4
W36
W23
W20
24O4
24O4C
TO 2T
XF MR
FLEXSYS BYPASS
DAMPER CONTROL
W37
W38
6
7
8
CTB2
=
=
* EVAP RESET TEMP
* FLEXSYS DIRTY FILTER SW.
TABLE 28 – MONITOR AND CONTROL I/O FOR MOD UNT CONTROLLER
I/O NAME
ANALOG OR
BINARY
SIGNAL
LEVELS
APPL. VALUE
RANGE
WHERE USED
System 1, Suction Pressure
AI
1.0-5.0V
0 to 200
X’Ducer Package
System 1, Discharge (Condenser) Pressure
AI
1.0-5.0V
0 to 500
X’Ducer Package
System 2, Suction Pressure
AI
1.0-5.0V
0 to 200
X’Ducer Package
System 2, Discharge (Condenser) Pressure
AI
1.0-5.0V
0 to 500
X’Ducer Package
System 3, Suction Pressure
AI
1.0-5.0V
0 to 200
X’Ducer Package
System 3, Discharge (Condenser) Pressure
AI
1.0-5.0V
0 to 500
X’Ducer Package
Cond. Fan, System 1
AO
0-10V
0 to 100%
Low Ambient
Cond. Fan, System 2
AO
0-10V
0 to 100%
Low Ambient
Cond. Fan, System 3
AO
0-10V
0 to 100%
Low Ambient