FlexSys Dewpt Reset
OFF
ON or OFF
Unit Setup
87
Exh Dmpr Pos For ON
%
80%
0-100%
Unit Setup
88
Exh Dmpr Pos For OFF
%
20%
0-100%
Unit Setup
89
OA Dmpr Pos For ON
%
60%
0-100%
Unit Setup
90
OA Dmpr Pos For OFF
%
20%
0-100%
Unit Setup
91
OAH Sensor Enable
OFF
ON or OFF
Unit Setup
92
RAH Sensor Enable
OFF
ON or OFF
Unit Setup
93
Exhaust Cntrl Offset
inwg
0.015 inwg
0.010 – 0.050
Unit Setup
94
Economizer Enable
ON
ON or OFF
Unit Setup
95
SAT Econo Loading
ON
ON or OFF
Unit Setup
96
Power Exhaust Enable
OFF
ON or OFF
Unit Setup
97
OA Flow Cntrl Enable
OFF
ON or OFF
Unit Setup
98
Comfort Vent Mode
OFF
ON or OFF
Unit Setup
99
Cmfrt Vent Max Dampr
%
75%
0-100%
Unit Setup
100
IAQ Sensor Enable
OFF
ON or OFF
Unit Setup
101
IAQ Sensor Span
ppm
5000
0 – 10000
Unit Setup
102
MAX DV Multiplier
1.25
2-Jan
Unit Setup
103
Altitude
Ft
1000
0-10000 Ft
Unit Setup
104
Morning Warm-Up
OFF
ON or OFF
Unit Setup
105
Max Warm-Up Time
min
120 min
0-240 min
Unit Setup
106
Pre-Occupancy Purge
OFF
ON or OFF
Unit Setup
107
Purge Schedule
4am - 5am
all days
Daily-Holiday
hh:mm start-end time
Unit Setup
108
Purge OAT High Limit
°F
85°
0°-110°F
Unit Setup
109
Purge OAT Low Limit
°F
55°
0°-110°F
Unit Setup
110
Smoke Purge Mode
0
0 – 5
Unit Setup
111
Internal Clk/Sched
OFF
ON or OFF
Unit Setup
112
Weekly Schedule
7am - 6pm
weekdays
8 start/stop entries
Unit Setup
113
Holiday Schedule
(No Sched)
16 entries
Unit Setup
114
Date and Time
(none)
dd-mm-year
hh:mm:ss am/pm
Unit Status
Description Text On OCC
Units
Default
Value
Value
Range
OCC
Key
NOTES:
1. Both gas and electric heat are referred to functionally as “stepped”
heating or heating “stages”; both HW (hot water) and steam are
functionally referred to as “hydronic” heat.
For Modulating Gas Heat "Heating Type" would be set to "HW".
TABLE 21 – SETPOINTS AND VALUES (CONTINUED)