TABLE 21 – SETPOINTS AND VALUES
* Continued on next page
Description Text On OCC
Units
Default
Value
Value
Range
OCC
Key
1
Unit Type
CV
CV, VAV, MIT-VAV
Confi guration
2
Dirty Filter Switch
OFF
ON or OFF
Confi guration
3
ASCD Override
OFF
ON or OFF
Confi guration
4
Run Test
OFF
ON or OFF
Confi guration
5
Panel Test
OFF
ON or OFF
Confi guration
6
# of Compressors
4
4 or 6
Confi guration
7
# of Heat Steps
0
0-6
Confi guration
8
Heating Type1
None
None, Gas, Electric,
Confi guration
9
Freezestat
OFF
ON or OFF
Confi guration
10
Transducer Package
0
0 – 3
Confi guration
11
Low Ambient Confi g
0
0 – 3
Confi guration
12
Dischrg Press Cntrl
psig
200 psig
100 – 200 psig
Confi guration
13
Sys Unloading Press
psig
400 psig
250-450 psig
Confi guration
14
Reset Lead-Lag
OFF
ON or OFF
Confi guration
15
SAT Temper Available
OFF
ON or OFF
Confi guration
16
Cooling SAT Limit #1
°F
45°F
40°-50°F
Confi guration
17
Cooling SAT Limit #2
°F
50°F
40°-65°F
Confi guration
18
Heating SAT Limit
°F
160°F
100°-195°F
Confi guration
19
Power Exhaust Confi g
0
0 - 3
Confi guration
20
Economizer Installed
NO
YES – NO
Confi guration
21
Airfl ow Meas Confi g
None
None, Full, Minimum, 1/4-3/4
Confi guration
22
AMS #1 Area
sq ft
3.33
0.00 – 24.00
Confi guration
23
AMS #1 K-Factor
0.75
0.500 – 1.000
Confi guration
24
AMS #2 Area
sq ft
10
9.00 – 18.00
Confi guration
25
AMS #2 K-Factor
0.75
0.500 – 1.000
Confi guration
26
Duct Sensor Hi Limit
inwg
5
2.5 – 5.0
Confi guration
27
Evaporator Damper
Installed = NO
YES
YES – NO
Confi guration
28
Sys X Comp Runtimes
starts
0
(> expected value)
Service
29
Sys X Comp Starts
hr
0
(> expected value)
Service
30
Exhaust (Fan Runtimes)
hr
0
(> expected value)
Service
31
AMS #1 Balancer Calculated Airfl ow
CFM
1
1 – 40000
Service
32
AMS #1 Controller Measured Air Flow at balance
CFM
1
1- 40000
Service
33
AMS #2 Balancer Calculated Airfl ow
CFM
1
1 - 40000
Service
34
AMS #1 Controller Measured Air Flow at balance
CFM
1
1- 40000
Service
35
Economizer Tunnis
Prop Band
Intes Time
°F
sec
40
45
0-100
0-1000
Service
36
Unoccupied Heating
°F
60°
45°-99°
Setpoint
37
Unoccupied Cooling
°F
85°
45°-99°
Setpoint
38
Occupied Heating
°F
68°
45°-99°
Setpoint
39
Occupied Cooling
°F
72°
45°-99°
Setpoint
40
VAV Cool High Temp
°F
60°
50°-70°
Setpoint
41
VAV Cool Low Temp
°F
55°
50°-70°
Setpoint
42
VAV Cool Reset Temp
°F
72°
60°-95°
Setpoint