3 Wiring and Connection
3.1.1 Main Circuit Terminals
3-2
3.1
Main Circuit Wiring
The names and specifications of the main circuit terminals are given below.
Also this section describes the general precautions for wiring and precautions under special environments.
3.1.1
Main Circuit Terminals
: Main circuit terminals
CN3
CN7
CN1
CN8
CN2
㧢
47
Terminal
Symbols
Name
Model SGDV-
Specification
L1, L2
Main circuit power in-
put terminals
F
Single-phase 100 to 115 V,
+10% to -15% (50/60 Hz)
L1, L2, L3
A
Three-phase 200 to 230 V,
+10% to -15% (50/60 Hz)
D
Three-phase 380 to 480 V,
+10% to -15% (50/60 Hz)
L1C, L2C
Control power input
terminals
F
Single-phase 100 to 115 V,
+10% to -15% (50/60 Hz)
A
Single-phase 200 to 230 V,
+10% to -15% (50/60 Hz)
24V, 0V
D
24 VDC,
15%
B1/ , B2
*1
External regenera-
tive resistor connec-
tion terminals
R70F, R90F, 2R1F,
2R8F, R70A, R90A,
1R6A, 2R8A
If the regenerative capacity is insufficient, connect
an external regenerative resistor between B1/ and
B2.
Note: The external regenerative resistor is not
included.
3R8A, 5R5A, 7R6A,
120A, 180A, 200A,
330A, 1R9D, 3R5D,
5R4D, 8R4D, 120D,
170D
If the internal regenerative resistor is insufficient,
remove the lead or shorting bar between B2 and B3
and connect an external regenerative resistor
between B1/ and B2.
Note: The external regenerative resistor is not
included.
550A, 260D
Connect a regenerative resistor unit between B1/
and B2.
Note: The regenerative resistor unit is not included.
Summary of Contents for SGDV SERVOPACK
Page 23: ...www dadehpardazan ir 88594014 15 xxii ...
Page 53: ...www dadehpardazan ir 88594014 15 2 Panel Operator 2 10 ...
Page 203: ...www dadehpardazan ir 88594014 15 5 Operation 5 11 5 Precautions for Safety Functions 5 86 ...
Page 275: ...www dadehpardazan ir 88594014 15 6 Adjustments 6 9 7 Position Integral 6 72 ...