TReX User Manual v15.30 Firmware
Main Screens
The TReX top icon bar provides information about the display screen and operating status.
The far right text indicates the selected main screen. This is either “IO” (inputs and outputs),
“PL” (PLC), “TX” (transmit) or “RX” (receive).
The time in the middle is the current RTC time (MENU->SYSTEM->TIME).
The “S” letter indicates that the master or slave SCADA telemetry modes are in operation.
The “M” letter, when present indicates that a Modbus telemetry request packet has been
processed within the last 2 seconds.
The “Incoming” down arrow indicates that the TReX is in receiving (absent
when RX is DISABLED). The “Outgoing” up arrow indicates that the TReX is
transmitting. The “B” icon indicates that the TReX is waiting to transmit but the
channel is currently busy.
The Icon “T” below indicates the TReX has been configured for telemetry
stand-alone “Back-to-Back Mirror Mode”.
The back to back arrows indicate the unit is operating in “Serial Link”
Telemetry mode.
The RJ45 connector icon is used to indicated when the TReX is TCP
connected. Flashes to the padlock icon when TLS security is enabled and in
use..
The chain link icon indicates when there is an active link to another device.
Each time a message is received this icon is shown. This icon is also
present immediately after start to ensure a link fail alert is not immediately
raised after startup.
The “X” indicates a loss of an active link. This occurs when there has been
no messages received for a configured period of time. The “link-fail” output
if enabled will operate when this icon is shown.
© WTE Limited, 2022 – Christchurch New Zealand
Page 17 of 302
Summary of Contents for TReX-460
Page 87: ...TReX User Manual v15 30 Firmware WTE Limited 2022 Christchurch New Zealand Page 87 of 302...
Page 286: ...TReX User Manual v15 30 Firmware WTE Limited 2022 Christchurch New Zealand Page 286 of 302...
Page 302: ...TReX User Manual v15 30 Firmware WTE Limited 2022 Christchurch New Zealand Page 302 of 302...