Parameters Configuration
120
NOTE!
• When setting the beam coding, the parameters must be configured on both the emitter
• To deactivate the beam coding, it must be deactivated on both the emitter and receiver
(see
9.4 Parametrization of the Receiver
The parameter configuration directly on the sensor takes place via the push buttons on the control panel.
Receiver
Menu down
Menu up
Apply
NOTE!
• If the parameter configuration is interrupted (e.g. due to an interruption in the power
supply), this causes the newly selected settings to be lost. In this case, the most recently
saved settings are active.
• To save changes to the parameter configuration permanently, the save function (see
Section 9.4.12, page 149) must be used to write them to the device memory via RUN
SAVE. Otherwise, the changes will be lost when the device is restarted.
• If parameters configuration is started from an error state, all settings are reset (see
).
9.4.1 Default Settings
Function
Default settings
Restart inhibit
Off (safety operating mode / automatic restart)
Contactor Monitoring
Off
Beam coding
Off
Cascading
Off
Muting
Off
Blanking
Off (full resolution)
Resolution
Full
When muting is activated:
Muting duration
300 s
Belt stop function
Off
Muting enable
Off
Direction setting
Off