5.2.4.7 Muting Functions
5.2.4.7.1 Combinable Muting Functions
Signal input and configuration
Parameters configuration
Muting types
MS1
MS2
MS3
MS4
Override
Muting enable
Belt stop
Full muting
enable
P
artial
muting
Direction setting
End due to
clearing of the ESPE
Gap suppression
Cross muting
X
X
−
−
X
X
0
0
X
−
X
X
2-sensor linear
muting
X
X
−
−
X
X
0
0
X
−
X*
X
4-sensor linear
muting with se-
quence monitoring
X
X
X
X
X
−
−
−
X
X
X
X
4-sensor linear
muting with time
monitoring
X
X
X
X
X
−
−
−
X
X
X
X
X : Additional function may be used
0 : Additional function may be used, but not at the same time as the other marked functions
− : Additional function may not be used
* : Function is activated automatically by the operating mode
NOTE!
All muting functions are parametrized on the receiver. The parametrization can take place
via the control panel or IO-Link.
5.2.4.7.2 Muting Duration
The maximum duration of a valid muting sequence is time-restricted to help prevent manipulation.
Once the maximum muting duration MMD has expired (300 seconds or 8 hours depending on the parametri-
zation), the muting is ended automatically and the safety function is active again.
Muting
active
Figure 12: Muting duration using cross-muting as an example