Project Engineering
70
Valid muting sequence:
Action
Comments
1. Muting start
MS1
MS2 are active
Both sensors must be activated within a
time frame of 4 seconds.
2. Muting active
MS1
MS2 are active
penetration
of the safety field
The safety field is interrupted, the OSSDs
remain in the ON state.
3. Muting active
MS1
MS2
penetration of the
safety field
MS3 active
Muting remains active.
4. Muting active
MS1
MS2
penetration of the
safety field
MS3
MS4 are active
MS3 and MS4 must be activated within a
time frame of 4 seconds.
5. Muting end
MS3 or MS4 are inactive or the maxi-
mum muting duration is reached.
Signal path
Muting
active
SF
penetration
Figure 11: Signal path for the 4-sensor linear muting with time monitoring