Safety Light Curtain
167
E 030
Receiver
Permanent
• Contactor short to
positive
• Contactor does not
drop
• Incorrect parameter
configuration
• Check the contactor
function
• Configure the EDM
parameters correctly
E 031
Receiver
Permanent
• Contactor short to
positive
• Contactor does not
deactivate
• Incorrect parameter
configuration
• Check the contactor
function
• Configure the EDM
parameters correctly
E 032
Receiver
Permanent
• Contactor short to
ground
• Contactor does not
activate
• Incorrect parameter
configuration
• Check the contactor
function
• Configure the EDM
parameters correctly
E 033
Receiver
Permanent
• Contactor short to
ground
• Contactor does not
activate
• Incorrect parameter
configuration
• Check the contactor
function
• Configure the EDM
parameters correctly
E 040
Receiver
Permanent
Ambient light: Emitter of
the same type detected
Remove the interfering
emitter
E 041
Receiver
Permanent
Ambient light: Emitter of
the same type detected
Remove the interfering
emitter
E 042
Receiver
Permanent
Ambient light: Potential
other cause
Check for and remove
any other extraneous
light sources
E 043
Receiver
Permanent
Ambient light: Potential
other cause
Check for and remove
any other extraneous
light sources
E 050
Emitter / re-
ceiver
Permanent
Parametrization not
complete
Repeat parametrization
E 051
Emitter / re-
ceiver
Permanent
Parametrization not
complete
Repeat parametrization
E 052
Receiver
Permanent
Safety field:
• Monitored blanking
• Object too small
• Incorrect parameter
configuration
• Check blanking
objects
• Repeat parametrization
E 053
Receiver
Permanent
Safety field:
• Monitored blanking
• Object too small
• Incorrect parameter
configuration
• Check blanking
objects
• Repeat parametrization