Safety Light Curtain
33
4.9.10 Muting Connection Box ZFBB001
The muting connection box ZFBB001 is connected to the extension connection of the ESPE. The following
functions can be implemented with the relevant parametrization of the ESPE:
• Confirmation of restart inhibit and override (connection of a button)
• Cascading (2-sensor muting and cascading are possible at the same time)
• 2-sensor muting
• 4-sensor muting
• Belt stop
• Muting enable
• Full Muting Enable
Port 5
Port 3
Port 1
Port 6
Port 4
Port 2
Port
Connection
Use
1
M12×1, 5-pin
MS3, belt stop/Full Muting Enable
2
M12×1, 5-pin
MS1
3
M12×1, 5-pin
MS4, Muting Enable
4
M12×1, 5-pin
MS2
5
M12×1, 8-pin
Cascading
6
M12×1, 5-pin
RES, override
Connection cable
Cable1 m, M12×1, 8-pin
Connection to extension connection ESPE
Further information can be found in the operating instructions for the ZFBB001.
NOTE!
• Cross-connections between muting signals must be prevented via protected routing of
cables. For further information, refer to EN ISO 13849-2, table D.4.
• All connections must be sealed with cables or blanking plugs (to retain the IP degree of
protection).