9�3
Overview of minimum intervals for inspection and maintenance
No�
Fueling nozzle
Inspection
Initial
(before com-
missioning
for the 1st
time)
Weekly
1
all TK17 H
2
Check external condition for
damage, irregularities, abnormal-
ities such as heavy ice formation,
deformation of the plastic protec-
tion and for cleanliness
X
X
2
all TK17 H
2
Check actuation lever for damage
and correct functioning
X
X
3
all TK17 H
2
Check locking lever for damage
and correct functioning
X
X
4
all TK17 H
2
Check swivel joint for correct
functioning
X
X
5
all TK17 H
2
Check fueling nozzle and media
inlet for leakage (see
)
X
X
6
TK17 H
2
with ENR
Check impact protection sleeve
for damage
X
X
7
TK17 H
2
with ENR
Check data interface for damage
and correct functioning
X
X
8
TK17 H
2
with ENR
Check label to ensure it is in
position and legible
X
X
9
TK17 H
2
without
ENR
Check impact protection for
damage
X
X
No�
Fueling nozzle
Maintenance
Monthly
After 3 years
or 20�000
cycles*
10
all TK17 H
2
Lubrication of the actuation (see
)
X
11
all TK17 H
2
Return to WEH for
in-factory maintenance
X
* whichever comes first
Note:
Component arrangement see
Chapter 3. Product overview / product description on
Î
If your application requires, set shorter intervals thanindicated above. A significant
shortening of the minimum intervals is particularly necessary if abnormalities are
found during the inspections.