- The leak test can begin under operating pressure using the
operating medium.
Î
Check the following measuring points (
)
- WEH
®
Service receptacle (1)
- impact protection sleeve and hand grip (2)
- Swivel joint and hand grip (3)
- Fitting (4)
Disconnection
Î
After the leak test has been completed and the hose has
been fully vented, disconnect the fueling nozzle.
Î
Pull the locking lever (Pos. 5) back in the direction of the
arrow (
) to release the locking mechanism and
move the actuation lever to the OFF position.
Î
Carefully pull the WEH
®
Service receptacle straight out of
the fueling nozzle (
Caution:
The WEH
®
Service receptacle may become cold
during leak testing. For this reason, you should wear
gloves when pulling the service receptacle out.
- If the measured ppm value is less than 1,000 ppm, the
fueling nozzle is ready to return to service.
Î
Replace the fueling nozzle back into the dispenser
mounting according to the instructions at the fueling
station.