Connecting Cables to Electronics Components
38
HPSA-7100-R Series Installation and User Manual
P/N P01- 04946 Rev C
Figure A.5, “Connecting Multiple HPSA-7100-R AMB’s Using a Single
NAC”
Figure A.8, “Dedicated SP40S with Multiple HPSAs”
Figure A.9, “Multi-Use SP40S with Multiple HPSAs (Class B Wiring
Shown)”
Figure A.10, “Combination FACP/SP40S and Multiple HPSAs”
Refer to Appendix C, "Driver/Speaker, Audio Input and Control Wire Gauge Distances"
for additional information with respect to identifying proper control wire gauges
distances.
5.2.1
Connect an External Audio System to the AMB
The HPSA-7100-R requires a minimum of two pairs of wires to be run from the External
Source. One pair connects from the audio output of the External Source to the HPSA’s
audio input, the other pair is used to activate the HPSA and connects to either the External
Source’s closed contact output or to the Notification Appliance Circuit’s (NAC) or
Sounder circuit’s output. Additionally, up to six pairs of cable should be connected to
monitor the Trouble state of the HPSA.
The HPSA-7100-R’s Audio Monitoring Bridge provides a User configurable 1 V
RMS
and
25 V
RMS
Audio Inputs. The optional HPSA-7100-V-KIT expands the configurations to
include 70.7 V
RMS
and 100 V
RMS
Audio Inputs.
70 V
RMS
and 100 V
RMS
Audio Inputs require optional module
HPSA-7100-V-KIT.
Designers and installers should consult with the external audio system
manufacturer and manufacturers of transient voltage surge suppressors for
proper selection and installation of primary protectors.
Field Wiring Considerations:
•
Audio Input: The HPSA-7100-R presents a load of 1/8 W maximum.
•
NAC Input: The maximum voltage is 40 V. The minimum activation
voltage is 9 V. The maximum current is 17 mA.
•
CC Input: Utilize dry CC output only. The activation resistance is 1 K
ohms or less; non-supervised - supervision to be provided by the
External System.
Figures in this section show a single Audio, NAC, Dry Contact and Trouble
connections for a single HPSA; refer to Figure A.5 in Appendix A for a
detailed wiring diagrams of connections using multiple HPSAs.
AC Power, Data and Audio cables should be placed in separate
conduits, to minimize the risk of interference.
Summary of Contents for HPSA-7100-R Series
Page 2: ...This page intentionally left blank...
Page 10: ...viii HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 16: ...xiv HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 20: ...xviii HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 22: ...xx HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 26: ...Preface xxiv HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 33: ...HPSA 7100 R Series Installation and User Manual 7 P N P01 04946 Rev C System Components...
Page 34: ...Introduction 8 HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 58: ...Installing the Cabinet 32 HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 174: ...148 HPSA 7100 R Series Installation and User Manual P N P01 04946 Rev C...
Page 178: ......