wc_tx003229gb_FM10.fm
88
Mobile Generator
Working with Basler Controller
8.13
Changing the Pre-Crank Time Delay (Glow Plug Timer)
Requirements
Machine stopped
Start switch in REMOTE START
Note: Internal programming of the genset controller, or closed connections to a
remote start switch, may cause the machine to start unexpectedly. Be prepared for
the engine to start even with the engine start switch in the REMOTE START
position.
Background
The genset controller includes a pre-crank time delay. This is the time the glow
plugs will be on before the engine starts to crank. The factory setting is 5 seconds.
The pre-crank time delay can be changed if desired.
NOTICE:
Do not set the glow plug timer to a value of more than 10. Damage to the
glow plugs may occur.
Procedure
Perform the procedure below to change the pre-crank time delay.
1. Press the right arrow button
(1)
to access the MAIN MENU.
2. Using the up/down arrow buttons
(2, 3)
highlight SETTINGS. Then, press the
right arrow button.
3. Highlight SYSTEM PARAMS. Then, press the right arrow button.
This procedure continues on the next page.
Summary of Contents for G 230
Page 1: ...5000186930 09 0215 5 0 0 0 1 8 6 9 3 0 Operator s Manual Mobile Generator G 230 G 240 EN ...
Page 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes ...
Page 178: ...wc_tx003849gb_FM10 fm 178 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770051 ...
Page 179: ...wc_tx003849gb_FM10 fm 179 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770052 ...
Page 180: ...wc_tx003849gb_FM10 fm 180 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770048 ...
Page 184: ...wc_tx003663gb_FM10 fm 184 Engine Maintenance T4i Cummins QSB6 7 770016 ...
Page 211: ...wc_tx003111gb_FM10 fm 211 User s Information for Transport Canada Fuel Tank ...
Page 212: ...wc_tx003111gb_FM10 fm 212 User s Information for Transport Canada Fuel Tank ...
Page 252: ......
Page 253: ......