How to Connect Loads
11.6
Connecting a 208V 3Ø Load and Multiple 120V 1Ø Loads
1. Stop the engine and turn the main circuit breaker off.
2. Set the voltage selector switch to the 240V position.
3. Open the lug door and connect the wires from the load as shown.
4. Close the lug door and start the machine.
5. Fine-tune the voltage as necessary using the voltage adjustment rheostat.
Note: Graphic is representative only. Your machine may vary.
WARNING
Electric shock hazard. High voltage can cause serious injury or death.
►
Connections must be made by a qualified electrician.
wc_gr011549
208 L-L
120 L-N
120V
120V
208V
208V
120V
120V
120V
208V
240V 3Ø
208V 3Ø
120V 1Ø
120V 1Ø
TO GND
LUG
HOT
HOT
HOT
GN
WH
When connecting multiple
120V loads:
Use L1 as "hot" for first load.
Use L3 as "hot" for second load.
Use L2 as "hot" for third load.
Balance the load
Summary of Contents for G 230
Page 1: ...5000186930 09 0215 5 0 0 0 1 8 6 9 3 0 Operator s Manual Mobile Generator G 230 G 240 EN ...
Page 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes ...
Page 178: ...wc_tx003849gb_FM10 fm 178 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770051 ...
Page 179: ...wc_tx003849gb_FM10 fm 179 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770052 ...
Page 180: ...wc_tx003849gb_FM10 fm 180 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770048 ...
Page 184: ...wc_tx003663gb_FM10 fm 184 Engine Maintenance T4i Cummins QSB6 7 770016 ...
Page 211: ...wc_tx003111gb_FM10 fm 211 User s Information for Transport Canada Fuel Tank ...
Page 212: ...wc_tx003111gb_FM10 fm 212 User s Information for Transport Canada Fuel Tank ...
Page 252: ......
Page 253: ......