wc_tx003618gb_FM10.fm
62
Mobile Generator
Operation (Basler Controller)
Continued from the previous page.
Using the
rheostat
The voltage adjustment rheostat
(d)
is used to fine-tune the voltage as needed
while the machine is running.
Care must be taken when using the voltage adjustment rheostat because adjusting
the voltage for 3-phase operation affects the voltage available at the single-phase
outlets. As the 3-phase voltage increases, so does the single-phase voltage.
NOTICE:
Do not use the GFCI or twist-lock receptacle (120V) when the 1Ø voltage
is above 135V. Damage to the receptacle and the tools connected to it may occur.
1
Do not use receptacle with this voltage.
2
Voltage may be too high for some tools and equipment. Check tool/equipment specifications.
Switch Position
3Ø Voltage
(L-L-L)
Corresponding 1Ø voltage
Twist lock receptacle
L-L (240V)
L-N (120V)
120V GFCI
240 VAC
208
208
120
120
220
220
125
125
240
240
139
1
139
1
480 VAC
480
240
139
1
139
1
460
230
133
2
133
2
wc_gr010391
d
Summary of Contents for G 230
Page 1: ...5000186930 09 0215 5 0 0 0 1 8 6 9 3 0 Operator s Manual Mobile Generator G 230 G 240 EN ...
Page 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes ...
Page 178: ...wc_tx003849gb_FM10 fm 178 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770051 ...
Page 179: ...wc_tx003849gb_FM10 fm 179 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770052 ...
Page 180: ...wc_tx003849gb_FM10 fm 180 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770048 ...
Page 184: ...wc_tx003663gb_FM10 fm 184 Engine Maintenance T4i Cummins QSB6 7 770016 ...
Page 211: ...wc_tx003111gb_FM10 fm 211 User s Information for Transport Canada Fuel Tank ...
Page 212: ...wc_tx003111gb_FM10 fm 212 User s Information for Transport Canada Fuel Tank ...
Page 252: ......
Page 253: ......