wc_tx003618gb_FM10.fm
65
Mobile Generator
Operation (Basler Controller)
Continued from the previous page.
7. Connect the load to the lugs and/or to the convenience receptacles.
8. Check the operation of the genset controller.
a. Set the engine start switch to REMOTE START. The LCD panel momentarily
displays
INITIALIZING
followed by
READY
.
Engine information is also
displayed. Check the fuel level and battery voltage. Add fuel and/or charge
the battery if needed. If the LCD display does not power up, check battery
voltage and connections.
b. With the READY screen showing, press the emergency stop button
(f)
. The
LCD panel displays
EMERGENCY STOP
, and the pre-alarm/alarm LED
illuminates. If the LCD does not display
EMERGENCY STOP
, do not
continue. Contact a Wacker Neuson dealer for assistance. Pull out the
emergency stop button after verifying the display.
c. Set the engine start switch to OFF.
Starting
9. Start the engine by setting the engine start switch to the START/RUN position.
After displaying
INITIALIZING
and
NOT IN AUTO
, the LCD panel will display
START DELAY
followed by
CRANKING
as the engine begins its crank cycle. The
crank cycle calls for the engine to crank for 15 seconds, then rest for 10 seconds.
This cycle will repeat three times in an attempt to start the engine.
If the engine does not start within three attempts, the genset controller stops the
crank cycle and
OVERCRANK
is displayed on the LCD panel.
To repeat the crank cycle, set the start switch to OFF, then back to START/RUN.
10.If equipped, set the idle switch to the operating speed position (rabbit).
Upon startup
Upon engine startup, the LCD displays the monitoring screen. Run the engine for a
few minutes to allow it to warm before turning on (closing) any circuit breakers.
Note: Leave the engine start switch (a) in the START/RUN position while the
generator is operating.
11.Check the voltage on the monitoring screen and adjust it as needed using the
voltage adjustment rheostat. See topic
Selecting the Voltage.
12.Turn on (close) the appropriate circuit breakers for your load.
wc_gr010195
Summary of Contents for G 230
Page 1: ...5000186930 09 0215 5 0 0 0 1 8 6 9 3 0 Operator s Manual Mobile Generator G 230 G 240 EN ...
Page 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes ...
Page 178: ...wc_tx003849gb_FM10 fm 178 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770051 ...
Page 179: ...wc_tx003849gb_FM10 fm 179 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770052 ...
Page 180: ...wc_tx003849gb_FM10 fm 180 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770048 ...
Page 184: ...wc_tx003663gb_FM10 fm 184 Engine Maintenance T4i Cummins QSB6 7 770016 ...
Page 211: ...wc_tx003111gb_FM10 fm 211 User s Information for Transport Canada Fuel Tank ...
Page 212: ...wc_tx003111gb_FM10 fm 212 User s Information for Transport Canada Fuel Tank ...
Page 252: ......
Page 253: ......