Mobile Generator
Using Remote Start Capabilities
12 Using Remote Start Capabilities
12.1
Remote Run Terminal Block
Location
The remote run terminal block
(a)
is located as shown.
Note: Graphic is representative only. Your machine may vary.
Description
The remote run terminal block provides connection points for the installation of a
remotely located transfer/start switch. If a transfer switch is installed, the generator
can be used as a stand-by power supply.
When connecting an Automatic Transfer Switch (ATS) or other remote switch:
■
Limit the distance between the remote run terminal block and the remote switch
to 1,219 m (4,000 ft) max.
■
Use twisted, 22-gauge wire or heavier.
■
Do not run the wire for the remote switch in the same conduit as current carrying
wire.
■
Do not run a voltage to the contacts (these are dry contacts).
wc_gr010366
4,000 ft
1,219 m
ATS
E
M
ERGENC
Y
S TO P
A
Ø
HZ
V
R
Basler
DIAGNOSTICS
DIAGNOSEN
DIAGNOSTICOS
DIAGNOSTICS
a
Summary of Contents for G 230
Page 1: ...5000186930 09 0215 5 0 0 0 1 8 6 9 3 0 Operator s Manual Mobile Generator G 230 G 240 EN ...
Page 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes ...
Page 178: ...wc_tx003849gb_FM10 fm 178 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770051 ...
Page 179: ...wc_tx003849gb_FM10 fm 179 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770052 ...
Page 180: ...wc_tx003849gb_FM10 fm 180 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770048 ...
Page 184: ...wc_tx003663gb_FM10 fm 184 Engine Maintenance T4i Cummins QSB6 7 770016 ...
Page 211: ...wc_tx003111gb_FM10 fm 211 User s Information for Transport Canada Fuel Tank ...
Page 212: ...wc_tx003111gb_FM10 fm 212 User s Information for Transport Canada Fuel Tank ...
Page 252: ......
Page 253: ......