wc_tx003619gb_FM10.fm
104
Mobile Generator
Operation (Deep Sea Controller)
9.5
Genset Controller Alarms and Shut-Down Conditions
Background
The genset controller monitors variables of engine and machine function. The
genset controller has two types of alarms: warning alarms and shut-down alarms.
The genset controller also monitors for electrical trip conditions.
Warning
alarms
Warnings are non-critical alarm
conditions that do not affect the operation
of the generator system. They serve to
draw the operator’s attention to an
undesirable condition. Warning alarms
are self-resetting when the fault condition
is removed.
Warning alarms include:
■
Low fuel level
■
High coolant temperature
■
Low oil pressure
■
Time to maintenance
During a warning alarm condition, the LCD panel displays the type of warning
alarm, the warning LED
(7)
illuminates, and an audible alarm sounds. The machine
is not shut down. Press the “Horn Reset” button to silence the audible alarm.
Shut-down
alarms
Shut-down alarms are latching alarms
and stop the generator. Shut-down
alarms include:
■
Low fuel level
■
High coolant temperature
■
Low oil pressure
■
Overspeed/Underspeed
■
Overcrank
■
Low coolant level (if equipped)
■
Overcurrent
During a shut-down alarm condition, the
LCD panel displays the type of alarm, the LEDs
(6, 8)
illuminate, an audible alarm
sounds, and the machine is shut down. Press the “Horn Reset” button to silence
the audible alarm. Remove the fault condition, then press “Stop/Reset”.
wc_gr011490
DSE
DEEP SEA ELECTRONICS
DSE 7310
7
STOP
wc_gr011491
DSE
DEEP SEA ELECTRONICS
DSE 7310
8
6
STOP
Variable
Normal
Warning
Shutdown
To Reset
Fuel level
>15%
15%
—
Fill fuel tank. Press “Stop/Reset”.
Coolant temp.
85°C±8
105°C
115°C
Add coolant. Press “Stop/Reset”.
Oil pressure
60–80 psi
20 psi
15 psi
Add engine oil. Press “Stop/Reset”.
Overspeed
60 Hz
—
66 Hz
Press “Stop/Reset”.
Underspeed
60 Hz
—
54 Hz
Press “Stop/Reset”.
Overcrank
—
—
After 3 attempts
Press “Stop/Reset”.
Time to maintain
500 hours
0 hours
—
Reset genset controller.
Coolant level
Above sender
—
Below sender
Add coolant. Press “Stop/Reset”.
Summary of Contents for G 230
Page 1: ...5000186930 09 0215 5 0 0 0 1 8 6 9 3 0 Operator s Manual Mobile Generator G 230 G 240 EN ...
Page 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes ...
Page 178: ...wc_tx003849gb_FM10 fm 178 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770051 ...
Page 179: ...wc_tx003849gb_FM10 fm 179 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770052 ...
Page 180: ...wc_tx003849gb_FM10 fm 180 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770048 ...
Page 184: ...wc_tx003663gb_FM10 fm 184 Engine Maintenance T4i Cummins QSB6 7 770016 ...
Page 211: ...wc_tx003111gb_FM10 fm 211 User s Information for Transport Canada Fuel Tank ...
Page 212: ...wc_tx003111gb_FM10 fm 212 User s Information for Transport Canada Fuel Tank ...
Page 252: ......
Page 253: ......