wc_tx003618gb_FM10.fm
67
Mobile Generator
Operation (Basler Controller)
7.13
LCD Panel: Monitoring Machine Operation
Overview
Generator and engine information is continuously monitored and displayed on the
LCD panel. The upper line displays generator information. The lower line displays
engine information.
Generator
information
The upper line of the LCD panel shows the voltage, phase, amperage, and
frequency of the electric power being generated. The information is shown only
when the engine is running.
This procedure continues on the next page.
wc_gr010202
Generator
Engine
Symbol
Meaning
Description
V
Volts
Displays the value of the AC output voltage being
produced by the generator.
Ø
Phase
Displays the leg or phase currently being monitored. In
three-phase mode, the display toggles between P1, P2,
and P3. In single-phase mode, the display toggles
between L1, L3, and L-L.
A
Amps
Displays the value of the AC output amperage
produced by the generator. If the generator is operating
at no load, output amperage will be zero (0).
HZ
Frequency in
Hertz
Displays the value of the output frequency. This display
will read approximately 61.5 Hz under a no-load
condition and approximately 60 Hz under load.
Summary of Contents for G 230
Page 1: ...5000186930 09 0215 5 0 0 0 1 8 6 9 3 0 Operator s Manual Mobile Generator G 230 G 240 EN ...
Page 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes ...
Page 178: ...wc_tx003849gb_FM10 fm 178 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770051 ...
Page 179: ...wc_tx003849gb_FM10 fm 179 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770052 ...
Page 180: ...wc_tx003849gb_FM10 fm 180 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770048 ...
Page 184: ...wc_tx003663gb_FM10 fm 184 Engine Maintenance T4i Cummins QSB6 7 770016 ...
Page 211: ...wc_tx003111gb_FM10 fm 211 User s Information for Transport Canada Fuel Tank ...
Page 212: ...wc_tx003111gb_FM10 fm 212 User s Information for Transport Canada Fuel Tank ...
Page 252: ......
Page 253: ......