wc_tx003229gb_FM10.fm
85
Mobile Generator
Working with Basler Controller
Continued from the previous page.
2. Using the up/down arrow buttons
(2, 3)
highlight SETTINGS. Then, press the
right arrow button.Highlight ALARM CONFIG. Then, press the right arrow
button.
3. Highlight ALARMS. Then, press the right arrow button.
4. Highlight the LOW FUEL LEVEL. Then, press the right arrow button.
5. Highlight the THRESHOLD. Then, press the check mark button
(5)
.
6. If you are not logged in, enter the password “OP”. Press the check mark button.
7. Using the up/down arrow buttons, change the value as desired. Press the check
mark button when finished.
8. Exit by pressing the left arrow button
(4)
three times or until the LCD displays
the SETTINGS menu. Then, scroll to LOGOUT and press the check mark
button. Press the left arrow button so that the READY screen appears.
Result
The low fuel alarm setting has now been changed.
Summary of Contents for G 230
Page 1: ...5000186930 09 0215 5 0 0 0 1 8 6 9 3 0 Operator s Manual Mobile Generator G 230 G 240 EN ...
Page 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes ...
Page 178: ...wc_tx003849gb_FM10 fm 178 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770051 ...
Page 179: ...wc_tx003849gb_FM10 fm 179 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770052 ...
Page 180: ...wc_tx003849gb_FM10 fm 180 Engine Maintenance John Deere 4045TF285 HF285 6068HF285 770048 ...
Page 184: ...wc_tx003663gb_FM10 fm 184 Engine Maintenance T4i Cummins QSB6 7 770016 ...
Page 211: ...wc_tx003111gb_FM10 fm 211 User s Information for Transport Canada Fuel Tank ...
Page 212: ...wc_tx003111gb_FM10 fm 212 User s Information for Transport Canada Fuel Tank ...
Page 252: ......
Page 253: ......