Operation
Lockout
The lockout state is described below.
Recycle
The recycle mode is described below.
State
Action or Function
Lockout
The burner will enter the lockout state for the following reasons:
Trial for ignition time has expired without flame being estab-
lished.
Cad cell detects flame at the end of the valve-on delay state.
Recycle time budget expires.
Relay check failure.
Note:
The burner control cannot reset by interrupting the
voltage.
During the lockout state:
The burner will not fire.
The red reset button / lockout light on the burner control will
flash during a soft lockout condition.
The reset button / lockout light will remain on continuously
during a hard lockout condition.
The burner fault light on the control panel will illuminate.
To clear the soft lockout fault so a restart can be attempted,
press and release the reset button.
Note:
After the third attempt
to manually clear the lockout fault, the burner control will enter
the hard lockout mode. To clear the hard lockout, press and
hold the reset button for 15 seconds.
wc_gr007665
Yellow
pump prime
Green
flame / recycle
Red
Reset button / lockout
State
Action or Function
Recycle
The burner will enter the recycle mode if the flame is lost while
the burner is firing.
During the recycle mode:
The burner control shuts down the burner.
The burner control enters a 60-second delay, then repeats
the ignition sequence.
The green flame / recycle light on the control panel flashes.
The burner control attempts to recycle each time the flame is
lost, up to three times. If flame is not established after the
third time, the burner control enters the hard lockout state.
To clear the hard lockout fault so a restart can be attempted,
press and hold the reset button for 15 seconds.
Summary of Contents for E3000
Page 6: ...Foreword wc_tx002028gb fm 6...
Page 39: ...ghi_tx001160gb fm 39 E 3000 Lifting and Transporting Notes...
Page 77: ...wc_tx001951gb fm 77 E 3000 Operation Notes...
Page 97: ...ghi_tx001162gb fm 97 E 3000 Accessories wc_gr008560 a b LR RR RS LS HX 50 HX 50...
Page 99: ...ghi_tx001162gb fm 99 E 3000 Accessories wc_gr008561 a LR LS HX 50...
Page 103: ...ghi_tx001162gb fm 103 E 3000 Accessories wc_gr008582 HX 100 HX 100 a b LR RR LS RS...
Page 105: ...ghi_tx001162gb fm 105 E 3000 Accessories wc_gr008583 HX 100 a LR LS...
Page 182: ...MSDS Dowfrost HD 50...
Page 186: ...wc_tx001673gb fm 186 Fuji Temperature Controller...
Page 199: ...Tire Safety Information...
Page 201: ...wc_tx001952gb fm 201 E 3000 Schematics 12 2 Composite Schematic Machine with Gas Burner...
Page 205: ...wc_tx001952gb fm 205 E 3000 Schematics 12 4 Circulation System Circuit...
Page 206: ...wc_tx001952gb fm 206 Schematics E 3000 12 5 Rewind System Circuit...
Page 207: ...wc_tx001952gb fm 207 E 3000 Schematics 12 6 Gas Train Schematic...
Page 208: ...wc_tx001952gb fm 208 Schematics E 3000 12 7 Generator...
Page 213: ......