Genset Maintenance
Onan Genset
Code
Fault Type
Corrective Action
1
High temperature fault
First-level fault; engine coolant temperature
exceeded 110°C (230°F).
1. Check engine coolant level and add coolant
as necessary.
2. Check for and remove any objects blocking
the air inlet or outlet openings in the bottom
and sides of the genset.
3. Flush the coolant system to remove debris
which may be clogging passages.
2
Low oil pressure fault
First-level fault; low oil pressure cutoff switch is
open.
1. Check the engine oil level and add oil as nec-
essary.
2. Drain any excess oil if the oil level is above
the “FULL” mark on the dipstick. (The oil will
foam if the level is too high which can lead to
the loss of oil pressure.)
3
Service check
First-level fault code signifying a second-level
code has occurred.
Check the second-level fault code by momen-
tarily pressing Stop. The second-level fault will
appear.
4
Over-crank fault
Cranking time without starting was exceeded.
1. Check fuel level; refill fuel tank.
2. Check for fuel leaks; repair as necessary.
3. Prime the engine fuel system by holding the
control switch at Stop for one minute.
4. Replace engine air filter.
5. Replace the fuel filter.
12
Over-voltage fault
The controller is not able to regulate to rated
voltage.
See authorized Cummins Onan dealer.
13
Under-voltage fault
The controller is not able to regulate to rated
voltage.
Turn off the line circuit breaker on the console. If
the genset now starts and runs, the load on the
genset is too great. Disconnect the extra loads.
14
Over-frequency fault
The controller is not able to regulate to rated
frequency.
1. Disconnect any extra loads.
2. Check for and repair fuel leaks. Air in the fuel
supply can disrupt frequency. Prime the
engine fuel system by holding the control
switch at Stop for one minute.
15
Under-frequency fault
The controller is not able to regulate to rated
frequency.
1. Disconnect any extra loads.
2. Check fuel level; refill fuel tank.
3. Check for and repair fuel leaks. Air in the fuel
supply can disrupt frequency. Prime the
engine fuel system by holding the control
switch at Stop for one minute.
4. Replace engine air filter.
5. Replace the fuel filter.
19
Governor actuator fault
The controller sensed that the actuator circuit
is either open or shorted
See authorized Cummins Onan dealer.
Summary of Contents for E3000
Page 6: ...Foreword wc_tx002028gb fm 6...
Page 39: ...ghi_tx001160gb fm 39 E 3000 Lifting and Transporting Notes...
Page 77: ...wc_tx001951gb fm 77 E 3000 Operation Notes...
Page 97: ...ghi_tx001162gb fm 97 E 3000 Accessories wc_gr008560 a b LR RR RS LS HX 50 HX 50...
Page 99: ...ghi_tx001162gb fm 99 E 3000 Accessories wc_gr008561 a LR LS HX 50...
Page 103: ...ghi_tx001162gb fm 103 E 3000 Accessories wc_gr008582 HX 100 HX 100 a b LR RR LS RS...
Page 105: ...ghi_tx001162gb fm 105 E 3000 Accessories wc_gr008583 HX 100 a LR LS...
Page 182: ...MSDS Dowfrost HD 50...
Page 186: ...wc_tx001673gb fm 186 Fuji Temperature Controller...
Page 199: ...Tire Safety Information...
Page 201: ...wc_tx001952gb fm 201 E 3000 Schematics 12 2 Composite Schematic Machine with Gas Burner...
Page 205: ...wc_tx001952gb fm 205 E 3000 Schematics 12 4 Circulation System Circuit...
Page 206: ...wc_tx001952gb fm 206 Schematics E 3000 12 5 Rewind System Circuit...
Page 207: ...wc_tx001952gb fm 207 E 3000 Schematics 12 6 Gas Train Schematic...
Page 208: ...wc_tx001952gb fm 208 Schematics E 3000 12 7 Generator...
Page 213: ......