05TA Service Manual
SERVICE OPERATIONS
7/24/13
9-3
Hand Expansion Valve.
The hand expansion valve is located after the
“A” solenoid valve. This valve should be set at a point where the float switch is open for a length of
time approximately equal to the time it is closed.
Freezer Pressure Switch.
The freezer pressure switch (FPS), located inside the control panel,
controls the freezing time period for the production of cylinder or crushed ice.
This switch was set at the factory to produce ice of recommended thickness. Look at the “Certificate
of Test” which was provided with the machine for a sample set of pressure readings with
corresponding time periods and water temperatures. Also see TABLE 11-6, Operating Vitals for
typical settings. Do not make adjustments until several ice discharging cycles have been completed.
FIGURE 9-3
Allen Bradley Pressure Switch
The following procedure is recommended for initially setting an AB pressure switch that has
not
been previously adjusted:
1. Turn the bottom screw (differential) approximately 1/2 turn to the Left (counter clockwise).
The pointer arrow, which is at the top middle of the switch, will be at the “F” setting.
2. Turn the top screw (range adjustment) approximately 4 1/2 turns to the Left (counter
clockwise). The pointer on the range setting will be between 40 psi and 50 psi.
3. After the machine is running, the range adjustment (top screw) will have to be fine-tuned to get
the proper ice thickness. (Clockwise = Thinner Ice) (Counter Clockwise = Thicker Ice)
The freezing time can be such that a small percentage of the ice is frozen solid. If so, some ice from
the top and bottom of the freezer should have a small hole in the center to insure that the freezing
time has not been extended to where a loss in capacity would result.
It is preferable that the freezing cycle be such that a small diameter hole remains in the center of the
ice cylinder. (1/16” diameter for 7/8” diameter ice, 1/8” diameter for 1 1/8” diameter ice, 1/4”
diameter for 1 3/8” diameter ice) This insures that the freezing cycle is not extended unnecessarily
and eliminates a possible opaque core in the center of the ice.
When crushed ice is produced, the freezer pressure switch (FPS) (FIGURE 9-3) should be set to
produce ice having a wall thickness of approximately 3/16”.
Turn top screw to adjust the pressure setting
(also referred to as the Range)
Clockwise = increase pressure setting (thinner ice)
Counterclockwise = decrease pressure setting (thicker ice)
Vogt Part #:
Summary of Contents for P118F/HE100
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 10: ...05TA Service Manual TABLE OF CONTENTS vi ...
Page 20: ...05TA Service Manual INTRODUCTION 7 19 13 1 10 ...
Page 40: ...05TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 7 14 3 18 BLANK PAGE ...
Page 50: ...5 6 5TA Service Manual START UP AND OPERATION 7 19 13 Blank page ...
Page 106: ...05TA Service Manual SERVICE OPERATIONS 3 10 14 9 28 Blank ...
Page 114: ...Blank page ...
Page 115: ...05TA Service Manual TABLES CHARTS 3 10 14 11 1 11 Tables Charts ...