Air-Cooled Units.
The condenser fan switch mounted to the frame (lower right side) (FIGURE 9-
5B) (CPS) is used to regulate the head pressure. This is an adjustable pressure switch located on the
right-hand front of machine. It controls the operation of the condenser fan motor(s) through a
contactor (FC) (FIGURE 6-2) located in the control panel. The switch is set to cycle the fan motor(s)
“On” at 210 psig and “Off” at 190 psig for R-22 and “On” at 250 psig and “Off” at 230 psig for R-
404a. Higher settings may be necessary for 0
°
F and below ambient conditions to assure there is
enough warm gas for ice harvesting.
FIGURE 9-5A
Water Regulating Valve
FIGURE 9-5B
Condenser Fan Switch
Vogt Part #:
Cut In Adjusting Screw
Set at 210 PSIG (R-22)
Set at 250 PSIG (R-404A)
(CW Lowers Setting)
Cut Out Adjusting Screw
Set at 190 PSIG (R-22)
Set at 230 PSIG (R-404A)
(CW Raises Setting)
Connected to
Compressor Discharge
Vogt Part #:
Adjusting Stem
Set at 200 PSI (R-22)
Set at 235 PSI (R-404A)
(CW Lowers Setting)
1 1/4” FPT Connection
(water connections)
Connected to High Side of
Water Cooled Condenser
CE Approved machine
Vogt Part #:
Summary of Contents for P118F/HE100
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 10: ...05TA Service Manual TABLE OF CONTENTS vi ...
Page 20: ...05TA Service Manual INTRODUCTION 7 19 13 1 10 ...
Page 40: ...05TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 7 14 3 18 BLANK PAGE ...
Page 50: ...5 6 5TA Service Manual START UP AND OPERATION 7 19 13 Blank page ...
Page 106: ...05TA Service Manual SERVICE OPERATIONS 3 10 14 9 28 Blank ...
Page 114: ...Blank page ...
Page 115: ...05TA Service Manual TABLES CHARTS 3 10 14 11 1 11 Tables Charts ...