SYMPTOM: Low compressor oil level.
POSSIBLE CAUSE
POSSIBLE REMEDY
Oil separator not returning oil.
Check oil separator float and oil return stop
valve (70) and line for a restriction. The oil
return
line
should
be
above
ambient
temperature most of the time as it returns oil.
It may be cooler at the start of a freeze cycle.
Repair or replace defective parts.
Repeated short cycling (refrigerant carrying oil
out of compressor).
Usually caused by freeze-up, low refrigerant
charge, low head pressure, faulty timer, faulty
pressure switch or expansion valve clogged.
Use process of elimination.
Worn piston rings.
This condition is hard to detect without
dismantling the compressor and checking
piston ring tolerances. Normally there will be a
little puddle of oil laying on top of the piston
when the head and valve plate are removed. It
is best to replace the compressor.
Summary of Contents for P118F/HE100
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 10: ...05TA Service Manual TABLE OF CONTENTS vi ...
Page 20: ...05TA Service Manual INTRODUCTION 7 19 13 1 10 ...
Page 40: ...05TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 7 14 3 18 BLANK PAGE ...
Page 50: ...5 6 5TA Service Manual START UP AND OPERATION 7 19 13 Blank page ...
Page 106: ...05TA Service Manual SERVICE OPERATIONS 3 10 14 9 28 Blank ...
Page 114: ...Blank page ...
Page 115: ...05TA Service Manual TABLES CHARTS 3 10 14 11 1 11 Tables Charts ...