05TA Service Manual
SERVICE OPERATIONS
3/10/14
9-4
High-Low Pressure Safety Switch.
The high-low pressure switch (HPS) (FIGURE 9-4) is a two pole dual
function switch. Located in the machine mounted to the frame near the compressor. It protects the machine
from possible damage due to abnormal pressure during operation.
! CAUTION !
When this switch causes the machine to stop, the cause should be
identified and corrected before resuming normal operation.
! CAUTION !
The
LOW
pressure cut-in should be set at 40 psig and the cutout set at 20 psig for R-22
The
LOW
pressure cut-in should be set at 52 psig and the cutout set at 28 psig for R-404a.
After tripping at the cutout setting, the switch will reset automatically when the pressure rises to the
cut-in setting.
The
HIGH
pressure cutout should be set at 300 psig for R-22 and 350 psig for R-404a. After
tripping, reset the switch manually.
FIGURE 9-4
High-Low Pressure Switch
If it becomes necessary to install a new high/low pressure switch, the following procedure is
recommended for its adjustment:
Turn the adjusting screws clockwise to raise the pressure setting. Turn counter-clockwise to lower
the setting. Adjust the switch to the indicated pressure settings and test with an accurate gage to be
sure the switch functions properly before installation.
Head Pressure.
The head pressure should be maintained at 190-210 psig for R-22 and 230-250 psig
for R-404a during the freeze cycle. This pressure can be checked at the test connection in the high
pressure line near the high-low pressure switch.
Water-Cooled Units.
A water regulating valve (FIGURE 9-5A) located in the condenser water inlet
line is used to control the water flow through the condenser. This valve should be adjusted to
maintain a head pressure of 195 psig for R-22 and 235 psig for R-404a. Increasing the water flow
lowers the head pressure and decreasing the water flow raises the head pressure. The valve is
adjusted during the factory test. The valve stem should not be opened as far as it will go or the valve
will not close fully when the head pressure drops below its setting.
Vogt Part #:
Reset Button
Range Adjusting Screw
Set at 40 PSIG (R-22)
Set at 52 PSIG (R-404A)
(CW Raises Setting)
High Pressure Adjustment
Set at 300 PSIG (R-22)
Set at 350 PSIG (R-404A)
(CW Raises Setting)
Differential Factory Set
Differential Adjusting Screw
Set at 20 PSIG
(CW Raises Setting)
Low Pressure
Test Connection
High Pressure
Test Connection
CE Approved machine
Vogt Part #: 12A2117D01CE
Summary of Contents for P118F/HE100
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 10: ...05TA Service Manual TABLE OF CONTENTS vi ...
Page 20: ...05TA Service Manual INTRODUCTION 7 19 13 1 10 ...
Page 40: ...05TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 7 14 3 18 BLANK PAGE ...
Page 50: ...5 6 5TA Service Manual START UP AND OPERATION 7 19 13 Blank page ...
Page 106: ...05TA Service Manual SERVICE OPERATIONS 3 10 14 9 28 Blank ...
Page 114: ...Blank page ...
Page 115: ...05TA Service Manual TABLES CHARTS 3 10 14 11 1 11 Tables Charts ...