05TA Service Manual
MAINTENANCE
7/19/13
7-3
Water Distributors.
The water distributors are located under the freezer cover (8) at the top of the
freezer. These distributors may require occasional or periodic cleaning to remove solids and foreign
particles accumulated from the make-up water. The frequency of this cleaning operation will depend
on the characteristics of the water supply. The cleaning operation is needed when the inside
diameter of a large proportion of the ice becomes irregular (due to channeling of water), or if some of
the ice is opaque, or if there is a noticeable decrease in ice capacity.
To clean distributors, stop the unit and remove the freezer cover (8) on top of the freezer. The water
distributors (one in each tube) may then be removed with pliers for cleaning. Use pliers on the
distributor’s top part with a twisting upward motion.
Note:
When re-installing distributors on the outside row, make sure holes are away from the gasket
Vogt Part #
Size Ice
Number of Tubes
Water Distributor
Freezer Cover
Freezer Cover Gasket
1”
156
1 1/4”
102
1 1/2”
72
Table 7-1
Number of Water Distributors Per Tube Size
Water Tank.
The production of opaque ice can indicate that the water in the water tank contains a
concentrated amount of solids or salts.
Remove cover plate. Open drain valve (39). Clean tank thoroughly by flushing out with a hose and
scrubbing with a stiff brush. Fill the water tank with fresh water.
When restarting the machine, be sure that the water pump is circulating water. It is possible that air
may have collected in the pump impeller housing and the pump may have to be stopped and started
several times to expel the air.
Water Cooled Condenser
Checking Operation.
Scheduled maintenance for water-cooled condensers is based primarily on
the operating conditions found at the machine. The condenser should be inspected at least annually
and cleaned as required. For extreme operating conditions where water quality is poor the condenser
may need to be cleaned several times a year. .
Proper operation of cooling towers will increase the interval between cleaning considerably. The
tower overflow rate should be checked frequently. If a tower is operated with insufficient overflow,
nominal 1-1/2 to 3 gallons per hour bleed depending on water quality, the resulting mineral
concentration in the water can cause rapid and heavy fouling inside the condenser tubes, requiring
excessively frequent cleaning. Also, these conditions often lead to severe corrosion.
Chemical
additives, including those to stop algae and related growths, should be obtained only from
a reputable, established supplier, and used specifically according to directions. Excessive treatment
of the water can cause more harm than good and the condensers, pumps, piping, and the towers
themselves may be damaged.
Summary of Contents for P118F/HE100
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 10: ...05TA Service Manual TABLE OF CONTENTS vi ...
Page 20: ...05TA Service Manual INTRODUCTION 7 19 13 1 10 ...
Page 40: ...05TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 7 14 3 18 BLANK PAGE ...
Page 50: ...5 6 5TA Service Manual START UP AND OPERATION 7 19 13 Blank page ...
Page 106: ...05TA Service Manual SERVICE OPERATIONS 3 10 14 9 28 Blank ...
Page 114: ...Blank page ...
Page 115: ...05TA Service Manual TABLES CHARTS 3 10 14 11 1 11 Tables Charts ...