05TA Service Manual
SERVICE OPERATIONS
7/24/13
9-18
Removal Of Refrigerant From The Machine.
To transfer the refrigerant charge from the machine
into a separate container, proceed as instructed above under “Pumpdown”. This will isolate most of
the refrigerant in the receiver and the recovery unit can be connected to the access port (44) of the
hand stop valve (58) at the bottom of the receiver. Open the valve access port by turning the valve
stem in (front seat) and operate the recovery unit until the system is considered empty.
! WARNING !
Approved recovery equipment, hoses, gages, and refrigerant containers must be
used to comply with all local and federal EPA regulations.
! WARNING !
! WARNING !
Follow these instructions carefully.
Severe personal injury can result from improper
discharge of refrigerant.
! WARNING !
! WARNING !
It is not recommended that refrigerant be transferred from a refrigeration system
into a cylinder. If such a transfer is made, the refrigerant cylinder must be an
approved CLEAN cylinder -- free of any contaminants or foreign materials--and
must be weighed continuously to assure contents do not exceed net weight specified
by cylinder manufacturer or any applicable code requirements.
! WARNING !
Refrigerant Leaks.
In addition to testing the machine for leaks as instructed under “Refrigerant
Charge”, it is advisable to again make a leak test after the unit has been in operation approximately
one week. Any noticeable change in operating conditions, other than shown on the “Certificate of
Test” may indicate a loss of refrigerant due to a leak. Always remove the refrigerant pressure from
the vessel or tubing before repairs are attempted.
Non-condensable Gases.
Satisfactory operation of the machine is not possible if non-condensable
gases (usually air) are present in the system. Excessive condensing pressure is an indication of such
gases. Excessive condensing pressure in water cooled condensers may also be due to the
accumulation of scale in the cooling coil or due to insufficient cooling water or excessive water
temperature. See “Water Cooled Condensers”, Section 7.
Summary of Contents for P118F/HE100
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 10: ...05TA Service Manual TABLE OF CONTENTS vi ...
Page 20: ...05TA Service Manual INTRODUCTION 7 19 13 1 10 ...
Page 40: ...05TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 7 14 3 18 BLANK PAGE ...
Page 50: ...5 6 5TA Service Manual START UP AND OPERATION 7 19 13 Blank page ...
Page 106: ...05TA Service Manual SERVICE OPERATIONS 3 10 14 9 28 Blank ...
Page 114: ...Blank page ...
Page 115: ...05TA Service Manual TABLES CHARTS 3 10 14 11 1 11 Tables Charts ...