85
1.
Vent the heating circuits.
2.
Check throughput of affected heating
circuits. Recommended temperature
differential between heating flow and
return approx. 8 K.
3.
Hydraulically balance the connected
heating circuits.
4.
Check the outside temperature sen-
sor (see page 95).
5.
Increase the set room temperature
for standard mode and match the
heating curves.
Operating instructions
6.
Enable heating operation via the inte-
gral instantaneous heating water
heater (if installed) (see page 84).
Troubleshooting
Steps if the room temperature is too low
5724 152 GB
Service