Required parameters for components connected on site
Pumps and other components
Pump/component
Parameter
Setting
Heating circuit pump
"System definition"
Ó
"System scheme 7000"
■ With heating circuit A1 (for
heating circuit without
mixer A1)
or
■ With heating circuit M2
(for heating circuit with
mixer M2)
DHW circulation pump
Extended menu:
"Time prog. DHW circ."
Setting a time program
Solar circuit pump
"Solar"
Ó
"Type solar control unit
7A00"
"4"
Circulation pump for
DHW reheating
"External heat source"
Ó
"Enable external heat
source 7B00"
"1"
"External heat source"
Ó
"Enable external heat
source for DHW 7B0D"
"1"
In conjunction with the
primary store system:
■ Cylinder primary pump
■ Motorised 2-way valve
"System definition"
Ó
"System scheme 7000"
With DHW heating
Extension kit for one
heating circuit with mixer
M2
"System definition"
Ó
"System scheme 7000"
With heating circuit M2
Note
Set rotary switch S1 in the
extension kit to "2" (see
extension kit installation
instructions).
Commissioning, inspection, maintenance
Further details regarding the individual steps