111
Parameter
Code
Delivered condi-
tion
Commis-
sioning
Internal hydraulics
Heat pump for drying a building
7300
0
Time program for screed drying
7303
0
Set flow temperature, external demand
730C
500 (
≙
50 °C)
Enable 3-way diverter valve heating/
DHW
730D
0
Operating mode secondary pump
7340
Do not adjust
Heating water buffer cylinder
Enable buffer cylinder/low loss header
7200
0
Temp. in operating status fixed value for
buffer cyl
7202
500 (
≙
50 °C)
Hysteresis temperature heating buffer
cylinder
7203
50 (
≙
5 K)
Max. temperature buffer cylinder
7204
600 (
≙
60 °C)
Temp. limit op. status fixed value for buf-
fer cylinder
7208
100 (
≙
10 °C)
Heating circuit 1
Standard room temperature
2000
200 (
≙
20 °C)
Reduced room temperature
2001
160 (
≙
16 °C)
Remote control
2003
0
Heating curve slope
2006
6 (
≙
0.6)
Heating curve level
2007
0 (
≙
0 K)
Influence room temperature hook-up
200A
10
Room temperature hook-up
200B
3
Max. flow temperature heating circuit
200E
400 (
≙
40 °C)
Room temperature in party mode
2022
200 (
≙
20 °C)
Heating circuit 2
Standard room temperature
3000
200 (
≙
20 °C)
Reduced room temperature
3001
200 (
≙
20 °C)
Remote control
3003
0
Heating curve slope
3006
6 (
≙
0.6)
Heating curve level
3007
0 (
≙
0 K)
Influence room temperature hook-up
300A
10
Room temperature hook-up
300B
3
Max. flow temperature heating circuit
300E
400 (
≙
40 °C)
Room temperature in party mode
3022
160 (
≙
16 °C)
Commissioning/service reports
Control parameters report
(cont.)
5724 152 GB
Service
Summary of Contents for AWS 104
Page 5: ...5 Certificates Declaration of conformity 119 Keyword index 120 Index Index cont 5724 152 GB...
Page 87: ...87 Opening programming unit 3 2 1 2x Troubleshooting Repairs cont 5724 152 GB Service...
Page 89: ...89 Removing separating plate 1 2 Troubleshooting Repairs cont 5724 152 GB Service...