60
Internal unit
X40
A
N
?
L1
N
?
L1
F1 T6,3 AH
1/N/PE
230 V/50 Hz
A
Wiring chamber, internal unit (luster
terminals, see page 41)
Connecting external unit power cable (230 V~)
■ Recommended power cable:
Type AWS/AWS-AC 104 and 107:
3 x 2.5 mm
2
Type AWS/AWS-AC 110:
3 x 4.0 mm
2
Type AWS/AWS-AC 113:
3 x 6.0 mm
2
■ Max. fuse rating 16 A
■ Economy tariff and power-OFF can be
used.
■ No parameters need to be set when
using economy tariff with power-OFF
facility. During the power-OFF period,
the compressor is shut down.