80
Commissioning without the commissioning assistant
Note
Type and extent of parameters depend
on the heat pump type, the selected sys-
tem scheme and the accessories used
(e.g. parameter for heating circuit M2:
display only if heating circuit M2 is con-
figured).
Activating service menu
The service menu can be activated from
any menu.
Press
OK
+
å
simultaneously for
approx. 4 s.
Disabling the service menu
The service menu remains active until it
is deactivated with
"Terminate serv-
ice?"
, or if no operation takes place for
30 minutes.
Setting parameters, using the exam-
ple "System scheme"
To set a parameter, first select the
parameter group and then the parame-
ters.
All parameters are displayed as plain
text. A parameter code is also assigned
to each parameter.
Service menu:
1. Press
OK
+
å
simultaneously for
approx. 4 s.
2. Select
"Coding level 1"
.
3. Select parameter group:
"System
definition"
4. Select parameter:
"System scheme
7000"
5. Adjust system scheme:
"6"
Alternatively, if the service menu was
already activated:
Extended menu
1.
å
2.
"Service"
3. Select
"Coding level 1"
.
4. Select parameter group:
"System
definition"
5. Select parameter:
"System scheme"
6. Confirm parameter code:
"7000"
7. Adjust system scheme:
"6"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5724 152 GB