45
Terminals
Function
Explanation
211.2
Secondary pump
Connection values
■ Max. output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4 (2) A
Connected at the factory.
■ In systems without a heating water buf-
fer cylinder, no other heating circuit
pump is required (see terminal 212.2)
■ Connect the temperature limiter as max-
imum temperature limiter for underfloor
heating circuit in series (see page 50).
211.4
M
r
3-way diverter valve
"Heating/DHW"
Connection values
■ Max. output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4 (2) A
3-way diverter valve connected at the fac-
tory; connect the cylinder primary pump on
site in parallel.
In conjunction with the pri-
mary store system:
■ Cylinder primary pump
M
■ 2-way shut-off valve
Controller and sensor PCB
D
Plug
Sensor
Type
F0
Outside temperature sensor
Ni500
(PTC)
F4
Buffer temperature sensor, top
Pt 500
(PTC)
F6
Cylinder temperature sensor, top
Pt 500
(PTC)
F7
Cylinder temperature sensor, bottom
Pt 500
(PTC)
F13
System flow temperature sensor (with sensor well, down-
stream of heating water buffer cylinder)
Pt500
(PTC)
F14
Flow temperature sensor, cooling circuit (direct heating
circuit A1 or separate cooling circuit)
Ni500
(PTC)
Installation sequence
Electrical connection
(cont.)
5724 152 GB
Installation