82
Pump/component
Parameter
Setting
Remote control (e.g.
Vitotrol 200A)
"Heating circuit 1"
Ó
"Remote control 2003"
or
"Heating circuit 2"
Ó
"Remote control 3003"
"1"
Note
Set code at the Vitotrol 200A
to assign heating circuits:
H1 for heating circuit 1
H2 for heating circuit 2
(see Vitotrol 200 A installa-
tion instructions)
Vitocom 100
"System definition"
Ó
"Vitocom 100 7017"
"1"
External extension H1
"System definition"
Ó
"External extension
7010"
"1"
Note
For parameters for external
hook-up, see the following
table.
External hook-up to external extension H1
External hook-up
Parameter
Setting
External demand
If necessary
"Internal
hydraulics"
Ó
"Flow temperature for
external demand 730C"
Set flow temperature for
external demand
External mixer OPEN
"System definition"
Ó
"Effect of external
demand on heat pump/
heating circuits 7014"
"0"
to
"7"
(Observe parameter
"Flow
temperature for external
demand 730C"
)
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5724 152 GB