126 - 23/May/97
6.3 WIRING AND GROUNDING
All the following cables must be shielded,
with 85% minimum shielding coverage:
- power motor cable (see Fig.6.2 and 6.3)
NOTES: if a power terminal board is used at motor
side, the shield must be RF connected to the
ground screw via the proper clip.
- connectors at motor side can have a threaded
clamp. Cable shield must be grounded in the same
way as in Fig.6.3.
- resolver cable (see Fig.2.3 and 6.3 motor
side)
FIG. 6.3 - GROUNDING OF SHIELD TO
CONNECTORS AT MOTOR SIDE
FIG. 6.2 - GROUNDING OF SHIELD TO
MOTOR CONNECTOR AT DRIVE SIDE
In case of Sub-D connector, cable shield
must be grounded to the metallic hood.
When there is not connector at drive side,
a kit with stand-off, screws and hose
clamps is provided.
The shield of the cable must be uncovered
from insulation coating and RF connected
to the stand-off through the hose clamp, as
in Fig.6.4.
- recovery resistor cable
- Reference, Enable and OK cable
- RS485 cable (flat cable between modules
excluded)
- simulated encoder cable (if applicable)
The shields of the cables must be
connected at both ends to the proper
housing via full circumferential bond to
metallic connectors or hose clamps.
FIG. 6.4 - GROUNDING OF SHIELD
WITHOUT CONNECTOR