SD500 Spindle Servo Drive Manual
63
stall detection warning is reported.
Table 4-36
Group F10.5x: Fault recovery protection
Parameter code
(Address)
Designation
Content
Default
(Setting range)
Adjustable
properties
F10.50
(0x0A32)
Fault
self-recovery
times
V/F SVC FVC PMVF PMSVC PMFVC
Set the allowable times of fault self-recovery to be
performed.
Note: 0 means to turn off the fault self-recovery function,
otherwise it means this function is on.
0
(0~10)
STOP
F10.51
(0x0A33)
Fault
self-recovery
interval time
V/F SVC FVC PMVF PMSVC PMFVC
Set the waiting time between a spindle drive failure and a
reset.
1.0s
(0~100.0)
STOP
F10.52
(0x0A34)
Number of recovered
faults
V/F SVC FVC PMVF PMSVC PMFVC
Indicate the number of fault self-recovery times that have
been performed; read-only.
0
READ
Table 4-37
4.11 Group F11: Operator Parameters
Group F11.0x: Key operation
Parameter code
(Address)
Designation
Content
Default
(Setting range)
Adjustable
properties
F11.00
(0x0B00)
Key lock selection
V/F SVC FVC PMVF PMSVC PMFVC
0: no lock
1: keyboard lock of function parameter modification
2: function parameters and non-start/stop key lock
3: function parameters and key full-lock
0
(0~3)
RUN
F11.01
(0x0B01)
Key lock password
V/F SVC FVC PMVF PMSVC PMFVC
Set key lock password.
0
(0~65535)
RUN
F11.04
(0x0B04)
Up/down
function
selection
V/F SVC FVC PMVF PMSVC PMFVC
Ones-bit: Up / down modification selection
0: invalid
1: used to adjust F01.09 frequency given via keyboard
2: used to adjust F13.01 PID given via keyboard
3: Keyboard up / down to modify the parameter number
0011
(0000~0213)
STOP