SD500 Spindle Servo Drive Manual
26
3: Channel A - Channel B
4: Channel A, channel B both maximum value
5: Channel A, channel B both minimum value
F01.08
(0x0108)
Frequency giving via
bundled commands
V/F SVC FVC PMVF PMSVC PMFVC
When this parameter is valid, it is used to set the frequency
source channel for each bundled command.
Ones-bit: Keyboard to bundle commands;
Tens-bit: Terminal to bundle commands;
Hundreds-bit: Communication to bundle commands;
Thousands-bit: Card to bundle commands;
0: No bundle
1: Keyboard number entering to give frequency;
2: Keyboard analog potentiometer to give frequency;
3: Voltage analog AI1 to give frequency;
4: Current/voltage analog AI2 to give frequency;
5: Reserved;
6: Terminal pulse PUL to give frequency;
7: Communication to give frequency;
8: Terminal UP/DW control;
9: PID control to give frequency;
A: Program control to give frequency;
B: Reserved;
C: Multi-Speed feeding;
0000
(0000~DDDD)
RUN
F01.09
(0x0109)
Frequency giving from
keyboard number
entering
V/F SVC FVC PMVF PMSVC PMFVC
Set and modify frequency via keyboard number entering.
50Hz
(0.00~ upper limit)
RUN
Table 4-5
Group F01.1x: Frequency command
Parameter code
(Address)
Designation
Content
Default
(Setting range)
Adjustable
properties
F01.10
(0x010A)
Max frequency
V/F SVC FVC PMVF PMSVC PMFVC
The maximum frequency that can be set for the spindle drive.
150.00Hz
(upper limit
frequency
STOP