SD500 Spindle Servo Drive Manual
52
(0x064B)
time
Set vY2 output OFF delay time.
(0.000~60.000s)
F06.76
(0x064C)
vY3 output OFF delay
time
V/F SVC FVC PMVF PMSVC PMFVC
Set vY3 output OFF delay time.
0.010s
(0.000~60.000s)
RUN
F06.77
(0x064D)
vY4 output OFF delay
time
V/F SVC FVC PMVF PMSVC PMFVC
Set vY4 output OFF delay time.
0.010s
(0.000~60.000s)
RUN
Table 4-26
4.9 Group F07: Running Control
Group F07.0x: Starting control
Parameter code
(Address)
Designation
Content
Default
(Setting range)
Adjustable
properties
F07.00
(0x0700)
Starting running
mode
V/F SVC FVC PMVF PMSVC PMFVC
0: Start from the starting frequency
1: DC braking first and then start from starting frequency
2: Start after speed tracking and direction judgment
0
(0~2)
STOP
F07.01
(0x0701)
Starting
pre-excitation time
V/F SVC FVC PMVF PMSVC PMFV
Only under vector control (without PG) on asynchronous
motors
0.00s
(0.00~60.00s)
STOP
F07.02
(0x0702)
Starting frequency
V/F SVC FVC PMVF PMSVC PMFVC
When the given frequency is lower than this value, it does
not start and is in standby mode.
0.50Hz
(0.00~
Upper limit
frequency via
number setting)
STOP
F07.03
(0x0703)
Starting protection
selection
V/F SVC FVC PMVF PMSVC PMFVC
0: off; 1:on
Ones-bit: Terminal starting protection on in case of
abnormal exit
Tens-bit: Jogging terminal starting protection on in case of
abnormal exit
Hundreds-bit: Terminal starting protection on when
command channel is switched to terminal
Thousands-bit:
Reserved
Note: When the free stop, emergency stop and forced stop
commands are valid, the terminal starting protection is
turned on by default, and the A.RUNx warning is reported
0111
(0000~1111)
STOP