vacon using macro mode and getting a quick start
6
6.3 Macro Mode Applications and Included Parameters
The tables below list the different applications and the Level 1 parameters included in the macro for that
application. The Factory Application macro is the core package (listed in Table 1); the other macros include
the Factory Application macro parameters as well as the ones listed in their respective tables (Tables 2, 3,
4, 5, and 6). The macro mode applications are as follows:
Factory Application (Table 1)
Fan Application (Table 2)
Fan with PI Application (Table 3)
Pump Application (Table 4)
Pump with PI Application (Table 5)
Vector Application (Table 6)
810 Language
Default: English
Range: 1-65535
Level 2, Macro
This parameter configures the language in which text strings will be displayed.
The following data values may be assigned to this parameter:
Parameter Value
English
Spanish
Para. #
Parameter Name
Default
See Page
001
Model Number
Read-only
102
Output Freq
Read-only
103
Output Voltage
Read-only
104
Output Current
Read-only
105
Drive Load
Read-only
106
Load Torque
Read-only
107
Drive Temp
Read-only
111
DC Bus Voltage
Read-only
201
Input Mode
Local Only
202
Rev Enable
Forward
301
Min Frequency
0.0 Hz
302
Max Frequency
60.0 Hz
303
Preset Freq 1
5.0 Hz
402
Accel Time 1
5.0 sec
403
Decel Time 1
5.0 sec
502
Voltage Boost
0.0%
610
Timed OL Select
Std Ind 60s
700
Vmet Config
Freq Out
705
Relay 1 Select
Drv Fault
706
Relay 2 Select
Drive Run
Table 1: Factory Application Macro
Summary of Contents for 500X
Page 1: ...vacon 500x ac drives user s manual ...
Page 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Page 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Page 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Page 123: ......