vacon 500x parameters
vacon
z
80
7
608 Restart Number
609 Restart Delay
Default: 0
Default: 60 sec
P608 Range: 0-8
P609 Range: 0-60 sec
Level 2
You may configure the drive to attempt to re-start a specified number of times after certain faults occur.
Chapter 8 lists all faults and notes which ones may be reset automatically.
The number of attempts at re-starting is set with parameter
608 (Restart Number). A
value of 0 prevents
the drive from attempting a re-start). The time duration that must elapse between re-start attempts is set
with parameter
609 (Restart Delay).
The type of start to be attempted is set with parameter
802 (Start
Options)
; see
).
If the number of attempted re-starts is exceeded, the drive will trip with a fault and will stop operating.
Resetting the fault can result in instant starting. (See page 111 for more information on faults and
troubleshooting.)
Note that for 2-wire operation, the FWD or REV terminal must still be active for the drive to attempt a re-
start.
Also note that the counter for attempted re-starts will not reset to zero until ten minutes after a successful
re-start.
610 Timed OL Select
Default: Std Ind 60s
Range: 0-7
Level 2
Two parameters in the Vacon 500x work together to configure how the motor timed overload operates:
parameter
510 (Rated Mtr FLA) and parameter 610 (Timed OL Select).
Parameter 510 (Rated Mtr FLA) should be configured to the value on the nameplate of the motor. This value
is used in calculating the percentage of current at which the drive is operating.
Set parameter 610 to one of the following data values to configure the desired overload characteristic:
Options
Trip Time Motor Type
Motor Class
Std Ind Shp
0 sec Standard Induction N/A
Std Ind 30s
30 sec Standard Induction 1
Std Ind 60s
60 sec Standard Induction 2
Std Ind 5mn
300 sec Standard Induction 10
In Duty Shp
0 sec Inverter Duty
N/A
In Duty 30s
30 sec Inverter Duty
1
In Duty 60s
60 sec Inverter Duty
2
In Duty 5mn
300 sec Inverter Duty
10
Parameter 610 (Timed OL Select) determines the graph of Trip (Fault) Time vs. Percent Current that is used
by the Motor TOL functionality. This protective feature is speed-dependent to handle standard induction
motors whose cooling is limited by the shaft-mounted fan. Blower-cooled motors and most inverter-duty
motors do not have this limitation.
UNINTENDED EQUIPMENT ACTION
Ensure that automatic re-starting will not cause injury to personnel or damage
to equipment.
Failure to observe this instruction can result in serious injury or equipment
damage.
ACTIONNEMENT INVOLONTAIRE DE L’APPAREIL
Assurez-vous qu’un redémarrage automatique n’entraînera ni des blessures a
personnel ni des dommages matériels.
Si cette directive n’est pas respectée, cela peut entraîner des blessures graves
des dommages matériels.
WARNING
AVERTISSEMENT
Summary of Contents for 500X
Page 1: ...vacon 500x ac drives user s manual ...
Page 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Page 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Page 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Page 123: ......