technical characteristics vacon
z
14
2
2.2 Power and Current Ratings
2.3 Environmental Specifications
2.4 Electrical Specifications
Vacon 0500 3L XXXX 5 (460 Vac Ratings)
Model number
Normal Duty
Input current (A)
Output current (A)
Heavy Duty
Input current (A)
Output current (A)
HP
kW
380 Vac
460 Vac
380 Vac
460 Vac
HP
kW
380 Vac
460 Vac
380 Vac
460 Vac
0009 5
5
4
12
8.8
8.9
7.6
3
2.2
7.2
5.6
5.1
4.8
0012 5
7.5
5.5
15
12.8
12
11
5
4
12
8.8
8.9
7.6
0016 5
10
7.5
19.7
16.3
15.6
14
7.5
5.5
15
12.8
12
11
0023 5
15
11
30.9
25.8
23
21
10
7.5
19.7
16.3
15.6
14
0031 5
20
15
40
33.3
31
27
15
11
30.9
25.8
23
21
0037 5
25
18
46.3
40
37
34
20
15
40
33.3
31
27
0043 5
30
22
57.5
47.8
43
40
25
18
46.3
40
37
34
0061 5
40
30
73.2
62.4
61
52
30
22
57.5
47.8
43
40
0071 5
50
37
82
78
71
65
40
30
73.2
62.4
61
52
0086 5
60
45
94
80
86
77
50
37
82
78
71
65
0105 5
75
55
114
99
105
96
60
45
94
80
86
77
0140 5
100
75
149
129
140
124
75
55
114
99
105
96
0168 5
125
90
168
156
168
156
100
75
140
124
140
124
0205 5
150
110
205
180
205
180
125
90
168
156
168
156
0240 5
200
132
240
240
240
240
150
110
205
180
205
180
Operating temperature
0 °C to +40 °C (32 °F to 104 °F)
Storage temperature
–20 °C to +65 °C (-4 °F to 149 °F)
Humidity
0% to 95% non-condensing
Altitude
1000 m (3300 ft) without derating
Maximum vibration
per EN50178 (1g @ 57-150 Hz)
Acoustic noise
80 dba sound power at 1 m (3 ft), maximum
Cooling
4 kW/5 HP models: Natural convection
5.5 to 132 kW/7.5 to 200.0 HP models: Forced air (temperature-controlled
external fan)
Input voltage
Vacon 0500 models: 380-460 Vac, 3 phase, +/- 15%
4-132 kW/5-200 HP
Line frequency
50 / 60 Hz ±2 Hz
Source kVA (maximum)
10 times the unit rated kVA, 65kA maximum (see note below)
DC bus voltage for:
Overvoltage trip
Dynamic brake activation
Nominal undervoltage (UV)
trip
230 Vac models
406 Vdc
388 Vdc
199 Vdc
460 Vac models
814 Vdc
776 Vdc
397 Vdc
Control system
V/Hz or Sensorless Vector Control (SVC)
Carrier frequency = 1 - 16 kHz, programmable; 8 kHz max. for 90-132 kW/125-
200 HP models
Output voltage
0 to 100% of line voltage, three-phase
Overload capacity
120% of rated RMS current for 60 seconds (normal duty rating)
150% of rated RMS current for 60 seconds (heavy duty rating)
Frequency range
0.1 to 400 Hz
Frequency stability
0.1 Hz (digital), 0.1% (analog) over 24 hours +/- 10 °C
Summary of Contents for 500X
Page 1: ...vacon 500x ac drives user s manual ...
Page 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Page 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Page 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Page 123: ......