702 Imet Config
Default: Drive Load
Range: n/a
Level 2
This parameter configures the analog signal that will be applied to the Imet output pin. The following data
values may be assigned to this parameter:
Para. Value
Description
Range Limit
Freq OutOutput frequency of the driveParameter max freq.
Voltage OutVoltage being supplied to the motor Rated motor voltage
Current OutCurrent being supplied to the motor 200% of drive rating
Drive LoadCalculated percentage of drive rating 200% of drive rating
Drive TempCalculation of total drive temp rating 100% of unit temp rating
Stator FreqCommanded frequency 100% of input config
Power OutCalculated power output of drive 250% of drive rating
+/- LoadPercentage torque of drive -200 to +200% of drive rating
PID FbackAllows the analog output to produce
a signal in proportion to the PID
feedback received.
Vin 1Mirrors the status of the Vin1 input
0-100%
Cin Mirrors the status of the Cin input
0-100%
Vin 2Mirrors the status of the Vin2 input
0-100%
SIO ConfigAllows the serial port to set the Imet
analog output through parameter 921
(SIO Imet Lvl) along with parameter 907
(Control Word)
EncoderMonitors the status of an encoder
connected to the drive through an option
board.
703 Imet Span
Default: 100%
Range: 0.0%-200.0%
Level 2
This parameter sets the span of the Imet analog output.
704 Imet Offset
Default: 0.0%
Range: 0.0%-90.0%
Level 2
This parameter sets the offset of the Imet analog output.
Summary of Contents for 500X
Page 1: ...vacon 500x ac drives user s manual ...
Page 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Page 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Page 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Page 123: ......