24-hour s358 (0)40 837 1150 • Email: [email protected]
vacon 500x parameters
vacon
z
68
7
Parameter
208, Cin Config,
selects the type of signal for analog input Cin. Parameters
and
may be used to customize the selected range. The following data values may be assigned
to this parameter:
Parameter Value
Description
4-20mA 50
4 to 20 mA current signal with 50 Ohm load
4-20mA 50I
4 to 20 mA current signal with 50 Ohm load Inverted
0-20mA 50
0 to 20 mA current signal with 50 Ohn load load
0-20mA 50I
0 to 20 mA current signal with 50 Ohm load Inverted
When the signal range is inverted (that is, the minimum input corresponds to the maximum output, while the maximum
input corresponds to the minimum output).
209 Cin Offset
Default = 0.0%
Range: 0.0% to 100.0%
Level: 2
Parameter
209, Cin Offset, configures the offset for analog input Cin expressed as a percentage of
the maximum value of the input signal. Note that if the input signal drops below the offset value or if the
input signal is lost (if no offset is configured), a fault will be generated.
210 Cin Span
Default = 100.0%
Range: 10.0% to 200.0%
Parameter
210, Cin Span,
is used to alter the range of the input signal for analog input Cin. For example, if
parameter
selects the 0 to 20 mA input signal, setting this parameter to 50% reduces it to
0 to 10 mA.
211 Vin2 Config
Default = 0-10 V
Range: n/a
Level: 2
Parameter
211, Vin2 Config,
selects the type of signal for analog input Vin2. Parameters
and
may be used to customize the selected range. The following data values may be
assigned to this parameter:
Parameter Value
Description
0-10V
0-10Vdc signal
0-10V Brk W
0-10Vdc signal with broken wire detection for speed pot operation
0-10V I
0-10Vdc signal inverted
0-10V Bipol
0-10Vdc signal (5Vdc is stop with 0Vdc Full REV and 10Vdc Full FWD
0-5V
0-5Vdc signal
0-5V I
0-5Vdc signal inverted
212 Vin2 Offset
Default = 0.0%
Range: 0.0% to 100.0%
Level: 2
Parameter
212, Vin2 Offset, configures the offset for analog input Vin2 expressed as a percentage of the
maximum value of the input signal. Note that if the input signal drops below the offset value or if
the input signal is lost (if no offset is configured), a fault will be generated.
213 Vin2 Span
Default = 100%
Range: 10.0 to 200.0%
Parameter
213, Vin2 Span,
is used to alter the range of the input signal for analog input Vin2. For example,
if parameter
selects the 0 to 10Vdc input signal, setting this parameter to 50% reduces it
to 0 to 5Vdc.
214 Vin1 Filter Time
Default = 20 ms
Range: 0 to 1000 ms
Level: 2
This parameter configures the time constant of a filter for the Vin1 analog input. When the parameter value
is set to 0 ms, there is no software filtering of the analog input. A value above 0 ms causes the drive to filter
the analog signal. Note that long filter times will create a delay in the drive response to signal changes.
215 Cin Filter Time
Default = 20 ms
Range: 0 to 1000 ms
Level: 2
This parameter configures the time constant of a filter of the Cin analog input. When the parameter value
is set to 0 ms, there is no software filtering of the analog input. A value above 0 ms causes the drive to filter
the analog signal. Note that long filter times will create a delay in the drive response to signal changes.
216 Vin2 Filter Time
Default = 20 ms
Range: 0 to 1000 ms
Level: 2
This parameter configures the time constant of a filter for the Vin2 analog input. When the parameter value
is set to 0 ms, there is no software filtering of the analog input. A value above 0 ms causes the drive to filter
the analog signal. Note that long filter times will create a delay in the drive response to signal changes.
Summary of Contents for 500X
Page 1: ...vacon 500x ac drives user s manual ...
Page 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Page 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Page 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Page 123: ......